Chapter IV Function Parameter Table
55
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F6 group: Digital terminal parameters
F6.00
Function
selection
of
multi-func
tion input
terminal
DI1
0: No function
1: Forward running FWD (edge+ level)
2: Reverse running REV (edge+ level)
3: Three-wire control Sin (level)
4: Forward jog (level)
5: Reverse jog (level)
6: Free stop (level)
7: Fault reset (edge signal)
8: Run pause (level)
9: External fault input
10: Frequency setting increase (UP)
11: Frequency setting decreases (DOWN)
12: Multistage speed terminal 1
13: Multistage speed terminal 2
14: Multistage speed terminal 3
15: Multistage speed terminal 4
16: Acceleration/deceleration time
selection 1
17: Acceleration/deceleration time
selection 2
18: PLC pause
19: PLC operation stop and reset
20: PID control pause
21: PID parameter switching
22: Counter trigger
23: Counter reset
24: Length reset
25: Acceleration/deceleration prohibited
(level)
26: Immediate DC braking
27: UP/DOWN setting cleared
28: Control command switched to keypad
29: Control command switched to
terminal
30: Control command switched to
communication
31: Frequency source switched to the
main frequency X
32: Frequency source switched to
auxiliary frequency Y
33: High-frequency pulse count reset
34
:
reserved
35
:
Water shortage signal
36
:
reserved
37
:
reserved
38
:
Fire override mode
39
:
Pump A maintenance signal
40
:
Pump B maintenance signal
1
1
×
F6.01
Function
selection
of
multi-func
tion input
terminal
DI2
2
F6.02
Function
selection
of
multi-func
tion input
terminal
DI3
7