Chapter IV Function Parameter Table
50
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F3.04 set range: 1.00
~
650.00Hz
F3.05 set range: 1
~
480V
1. Set the parameters of the controlled
asynchronous motor.
2. In order to ensure the control
performance, make sure to set the values
of F3.01
~
F3.05 correctly according
to the nameplate parameters of the
asynchronous motor.
3. This drive provides parameter
self-tuning function. The accurate
parameter self-tuning comes from the
accurate settings of the motor nameplate
parameters.
4. In order to ensure the control
performance, please configure the motor
according to the standard adapter motor of
the drive. If the gap between the motor
power and the standard adapter motor is
too large, the control performance of the
drive will decrease significantly.
F3.02
Rated
current
0.1A
×
F3.03
Rated
speed
1rpm
×
F3.04
Rated
frequency
0.01Hz
×
F3.05
Rated
voltage
1V
×
F3.06
No-load
current I0
F3.06 set range: 0.1
~
6553.5A
F3.07 set range: 0.000
~
50.000Ω
F3.08 set range: 0.0
~
6553.5mH
F3.09 set range: 0.000
~
50.000Ω
F3.10 set range: 0.0
~
6553.5mH
1. After changing the motor model code
F3.00, the drive automatically sets the
parameters of F3.06
~
F3.10 to the
parameters of the corresponding motor.
2. If the parameters of the motor are
known, please write the values in
F3.06
~
F3.10 accordingly. If the motor
parameter self-tuning is performed, the set
values of F3.06
~
F3.10 will be
updated automatically after the tuning is
completed normally.
3. These parameters are the reference
parameters for drive control and have
direct impact on control performance.
Note: Users shall not change this group
of parameters at random.
0.1A
Model
determina
tion
×
F3.07
Stator
resistance
R1
0.001Ω
○
F3.08
Leakage
inductance
X
0.1mH
○
F3.09
Rotor
resistance
R2
0.001Ω
○
F3.10
Mutual
inductance
Xm
0.1mH
○
F3.11
Motor
poles
2~14
2
4
×