Chapter V Basic Operation Instructions
104
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
protection state. The drive will not run until
the run command terminal is canceled and
then the terminal is enabled.
1: If the run command is valid, the drive
speed tracking starts.
Note: For safety, be cautious when setting
to 1.
F2.07
Start
protection
wait time
Set range: 0.0
~
10.0s
0.1s
0.0s
○
F2.30
Forward and
reverse dead
zone time
Set range: 0.00
~
360.00s
0.01s
0.01s
×
F6.09
Forward/rev
erse running
mode setting
0: Two-wire control mode 1: This mode is
the most commonly used two-wire mode.
The forward and reverse of the motor are
determined by the defined FWD and REV
terminal commands.
1: Two-wire control mode 2: This mode
uses the defined FWD as the running
terminal and the direction is determined by
the REV status that defined.
2: Three-wire control mode 1: This mode
uses the defined Sin as the enable terminal,
the run command is generated by FWD or
REV, and both control the operation
direction. When the drive operates, the
terminal Sin must be closed. The terminal
FWD or REV generates a rising edge signal
to control the operation and direction of the
drive. When the drive stops, the terminal
Sin must be disconnected to complete the
stop.
3: Three-wire control model 2: This mode
uses the defined Sin as the enable terminal,
the run command is generated by FWD, and
1
0
×