Chapter IV Function Parameter Table
45
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
The process of brake first and then restart
from the start frequency, as shown in the
figure: When the drive is put into
operation, first perform the DC braking
before starting according to the DC
braking current and the DC braking time
set by F2.03 and F2.04; then start from
this frequency and operate the set time
according to the regulations of F2.01 and
F2.02; then enter the normal acceleration
phase according to parameters such as the
set acceleration and deceleration times,
the acceleration and deceleration time
methods, etc. and accelerate to the set
frequency.
F2.04
Start DC
braking
time
0.1s
0.0s
○
F2.05
Accelerati
on/deceler
ation mode
selection
0: Linear acceleration/deceleration: The
output frequency increases or decreases
linearly
1: Reserved
1
0
×
F2.06
Start
protection
selection
(only valid
for
two-wire
control)
This function realizes whether the drive
automatically starts running when the
drive is powered on, the fault is cleared,
or the command channel is switched to
the terminal two-wire mode.
0: If the run command is valid, the drive
does start, and the drive is in the running
protection state. The drive will not run
until the run command terminal is
canceled and then the terminal is enabled.
1: If the run command is valid, the drive
speed tracking starts.
1
0
×