Chapter V Basic Operation Instructions
129
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value Change
F9.02
Multistage
instruction 1
Lower limit frequency ~ upper limit
frequency
0.01Hz
20.00Hz
○
F9.03
Stage 1
instruction
setting
LED single digit:
0: Multistage instruction 1 (F9.02)
1: AI1
2: AI2
3: Pulse frequency
4: Communication
5: Keypad digital potentiometer
input
6: Reserved
LED tens digit:
0: Acceleration/deceleration time 1
1: Acceleration/deceleration time 2
2: Acceleration/deceleration time 3
3: Acceleration/deceleration time 4
LED hundreds digit:
0: Forward running
1: Reverse running
Note: Only the LED single digit
frequency source of stage 1
instruction can be set.
111
005
○
F9.04
Stage 1
instruction
running time
Set range: 0.1
~
6000.0
Note: For the time unit selection, see
F9.00 hundreds digit setting.
0.1
10.0
○
F9.05
Multistage
instruction 2
Stage X instruction (F9.05, F9.08,
F9.11, F9.14, F9.17, F9.20, F9.23,
F9.26, F9.29, F9.32, F9.35
、
F9.38,
F9.41, F9.44, and F9.47) setting range:
Lower limit frequency ~ upper limit
frequency
Stage X instruction (F9.06, F9.09,
F9.12, F9.15, F9.18, F9.21, F9.24,
F9.27, F9.30, F9.33, F9.36
、
F9.39,
F9.42, F9.45, and F9.48) setting range:
LED single digit:
0: Multistage instruction x
1: Reserved
LED tens digit:
0: Acceleration/deceleration time 1
1: Acceleration/deceleration time 2
2: Acceleration/deceleration time 3
3: Acceleration/deceleration time 4
LED hundreds digit:
0: Forward running
1: Reverse running
Stage X instruction running time (F9.07,
F9.10, F9.13, F9.16, F9.19, F9.22,
F9.25, F9.28, F9.31, F9.34, F9.37
、
F9.40, F9.43, F9.46, and F9.49) setting
range:
0.01Hz
20.00Hz
○
F9.06
Stage 2
instruction
setting
111
000
○
F9.07
Stage 2
instruction
running time
0.1
10.0
○
F9.08
Multistage
instruction 3
0.01Hz
20.00Hz
○
F9.09
Stage 3
instruction
setting
111
000
○
F9.10
Stage 3
instruction
running time
0.1
10.0
○
F9.11
Multistage
instruction 4
0.01Hz
20.00Hz
○
F9.12
Stage 4
instruction
setting
111
000
○
F9.13
Stage 4
instruction
running time
0.1
10.0
○
F9.14
Multistage
instruction 5
0.01Hz
20.00Hz
○