Chapter V Basic Operation Instructions
145
Related parameter table:
Parameter
Code
Parameter
name
Parameter detailed description
Factory
value
Change
U1.00
Historical
fault
number
Set range: 0
~
9
According to the setting of this function code, you
can view the fault record information of the last 10
times. By setting different values within
U1.01
~
U1.06, the corresponding fault record will
display.
0
○
U1.01
Fault code
during fault
Fault record information at the xth fault (x is the set
value of U1.00)
-
*
U1.02
Bus voltage
during fault
-
*
U1.03
Output
current
during fault
-
*
U1.04
Running
frequency
during fault
-
*
U1.05
Running
temperature
during fault
-
*
U1.06
Fault
occurrence
time
-
*
Fault alarm content and countermeasure table:
Fault
code
Fault type
Possible cause of
failure
Countermeasures
E001
Drive
accelerated The acceleration time is Extend the acceleration time