Chapter IV Function Parameter Table
54
Parameter
Code
Parameter
name
Parameter detailed description
Minimum
Unit
Factory
value
Change
F5.29 set range: F5.27
~
100.0%
F5.30 set range: 0.00
~
50.00KHz
F5.31 set range: 0.0
~
F5.33
F5.32 set range: 0.00
~
10.00V
F5.33 set range: F5.31
~
100.0%
F5.34 set range: 0.00
~
10.00V
F5.35 set range: 0.0
~
F5.37
F5.36 set range: 0.00
~
10.00V
F5.37 set range: F5.35
~
100.0%
F5.38 set range: 0.00
~
10.00V
1. The function code defines the
corresponding relationship between the
output value and the analog output. When
the output value exceeds the set maximum
output or minimum output range, it will
be calculated as either upper limit output
or lower limit output.
2. When the analog output is current
output, 1mA current is equivalent to 0.5V
voltage.
3. In different applications, the analog
output corresponding to 100% of the
output value is different. The following
legend illustrates the different settings:
Note: AO1 supports 0~10V/0~20mA
output (selected by jumper J3), and
AO2 supports 0~10V/0~20mA output
(selected by jumper J4).
F5.28
HDO
output
frequency
correspond
ing to
lower limit
0.01KHz 0.00KHz
○
F5.29
HDO
output
upper limit
0.1%
100.0%
○
F5.30
HDO
output
frequency
correspond
ing to
upper limit
0.01KHz 50.00KHz
○
F5.31
AO1
output
lower limit
0.1%
0.0%
○
F5.32
AO1
output
voltage
correspond
ing to
lower limit
0.01V
0.00V
○
F5.33
AO1
output
upper limit
0.1%
100.0%
○
F5.34
AO1
output
voltage
correspond
ing to
upper limit
0.01V
10.00V
○
F5.35
AO2
output
lower limit
0.1%
0.0%
○
F5.36
AO2
output
voltage
correspond
ing to
lower limit
0.01V
0.00V
○
F5.37
AO2
output
lower limit
0.1%
100.0%
○
F5.38
AO2
output
voltage
correspond
ing to
upper limit
0.01V
10.00V
○
F5.39
Reserved -
-
-
*
F5.40
Reserved -
-
-
*