B-50
D60 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7671
...Repeated for module number 16
7690
...Repeated for module number 17
76AF
...Repeated for module number 18
76CE
...Repeated for module number 19
76ED
...Repeated for module number 20
770C
...Repeated for module number 21
772B
...Repeated for module number 22
774A
...Repeated for module number 23
7769
...Repeated for module number 24
Thermal Overload Protection (Read/Write Settings) (2 Modules)
7788
Thermal Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
7789
Thermal Protection 1 Source
0 to 5
---
1
F167
0 (SRC 1)
778A
Thermal Protection 1 Base Current
0.2 to 3
pu
0.01
F001
80
778B
Thermal Protection 1 K Factor
1 to 1.2
---
0.05
F001
110
778C
Thermal Protection 1 Trip Time Constant
0 to 1000
min.
1
F001
45
778D
Thermal Protection 1 Reset Time Constant
0 to 1000
min.
1
F001
45
778E
Thermal Protection 1 Minimum Reset Time
0 to 1000
min.
1
F001
20
778F
Thermal Protection 1 Reset
0 to 4294967295
---
1
F300
0
7791
Thermal Protection 1 Block
0 to 4294967295
---
1
F300
0
7793
Thermal Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7794
Thermal Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
7795
Reserved (2 items)
---
---
---
F001
0
7797
Repeated for Thermal Protection 2
Broken Conductor Detection (Read/Write Settings) (2 or 6 Modules)
77AA
Broken Conductor 1 Function
0 to 1
---
1
F102
0 (Disabled)
77AB
Broken Conductor 1 Source
0 to 5
---
1
F167
0 (SRC 1)
77AC
Broken Conductor 1 I2/I1 Ratio
20 to 100
%
0.1
F001
200
77AD
Broken Conductor 1 I1 Minimum
0.05 to 1
pu
0.01
F001
10
77AE
Broken Conductor 1 I1 Maximum
0.05 to 5
pu
0.01
F001
150
77AF
Broken Conductor 1 Pickup Delay
0 to 65.535
s
0.001
F001
20000
77B0
Broken Conductor 1 Block
0 to 4294967295
---
1
F300
0
77B2
Broken Conductor 1 Target
0 to 2
---
1
F109
0 (Self-reset)
77B3
Broken Conductor 1 Events
0 to 1
---
1
F102
0 (Disabled)
77B4
Reserved (2 items)
---
---
---
F001
0
77B6
...Repeated for Broken Conductor 2
Ohm Inputs (Read/Write Setting) (2 Modules)
77F8
Ohm Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
77F9
Ohm Inputs 1 ID
---
---
---
F205
"Ohm Ip 1 "
77FF
Ohm Inputs 1 Reserved (9 items)
0 to 65535
---
1
F001
0
7808
...Repeated for Ohm Inputs 2
Phasor Measurement Unit Recorder Config Counter Command (Read/Write Command)
781A
PMU 1 Recorder Clear Config Counter
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit One-shot Command (Read/Write Setting)
788C
PMU One-shot Function
0 to 1
---
1
F102
0 (Disabled)
788D
PMU One-shot Sequence Number
0 to 99
---
1
F001
1
788E
PMU One-shot Time
0 to 235959
---
1
F050
0
Phasor Measurement Unit Recording Values (Read Only)
7890
PMU 1 Available Records
0 to 65535
---
1
F001
0
7891
PMU 1 Second Per Record
0 to 6553.5
---
0.1
F001
0
7893
PMU 1 Last Cleared Date
0 to 400000000
---
1
F050
0
Phasor Measurement Unit Test Values (Read/Write Setting)
78AE
PMU 1 Test Function
0 to 1
---
1
F102
0 (Disabled)
78AF
PMU 1 Phase A Voltage Test Magnitude
0 to 700
kV
0.01
F003
50000
78B1
PMU 1 Page A Voltage Test Angle
-180 to 180
°
0.05
F002
0
Table B–10: MODBUS MEMORY MAP (Sheet 42 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...