GE Multilin
D60 Line Distance Protection System
2-3
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2.1.2 SECURITY
The following security features are available:
•
Password security — Basic security present in the default offering of the product
•
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
•
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
a) ENERVISTA SECURITY
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a substa-
tion and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security management
system is disabled by default to allow the administrator direct access to the EnerVista software after installation. It is recom-
mended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
b) PASSWORD SECURITY
Password security is a basic security feature present in the default offering of the product.
Two levels of password security are provided: command and setting.
The following operations are under command password supervision:
•
Operating the breakers via faceplate keypad
•
Changing the state of virtual inputs
•
Clearing the event records
•
Clearing the oscillography records
•
Clearing fault reports
•
Changing the date and time
•
Clearing the breaker arcing current
Table 2–2: OTHER DEVICE FUNCTIONS
FUNCTION
FUNCTION
FUNCTION
Breaker arcing current (I
2
t)
Fault locator
Synchrophasors
Breaker control
FlexElements™ (8)
Time synchronization over IRIG-B or
IEEE 1588
Breaker flashover
FlexLogic equations
Time synchronization over SNTP
Contact inputs (up to 96)
IEC 60870-5-103 communications
(optional)
Transducer inputs and outputs
Contact outputs (up to 64)
IEC 61850 communications (optional)
Trip bus
Control pushbuttons
Line pickup
User-definable displays
CyberSentry™ security
Load encroachment
User-programmable LEDs
Data logger
Metering: current, energy, frequency,
power, power factor, voltage
User-programmable pushbuttons
Digital counters (8)
Modbus user map
User-programmable self-tests
Digital elements (48)
Non-volatile latches
Virtual inputs (64)
Direct inputs and outputs (32)
Non-volatile selector switch
Virtual outputs (96)
Disconnect switches (16)
Open pole detector
VT fuse failure
DNP 3.0 or IEC 60870-5-104 Comms
Oscillography
Event recorder
Pilot schemes
Fault detector and fault report
Setting groups (6)
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...