8-24
D60 Line Distance Protection System
GE Multilin
8.5 SINGLE-POLE TRIPPING
8 THEORY OF OPERATION
8
8.5.2 PHASE SELECTION
The D60 uses phase relations between current symmetrical components for phase selection. First, the algorithm validates
if there is enough zero-sequence, positive-sequence, and negative-sequence currents for reliable analysis. The compari-
son is adaptive; that is, the magnitudes of the three symmetrical components used mutually as restraints confirm if a given
component is large enough to be used for phase selection. Once the current magnitudes are validated, the algorithm ana-
lyzes phase relations between the negative-sequence and positive-sequence currents and negative-sequence and zero-
sequence currents (when applicable) as illustrated below.
Figure 8–10: PHASE SELECTION PRINCIPLE (ABC PHASE ROTATION)
Due to dual comparisons, the algorithm is very secure. For increased accuracy and to facilitate operation in weak systems,
the pre-fault components are removed from the analyzed currents. The algorithm is very fast and ensures proper phase
selection before any of the correctly set protection elements operates.
Under unusual circumstances such as weak-infeed conditions with the zero-sequence current dominating during any
ground fault, or during cross-country faults, the current-based phase selector may not recognize any of the known fault pat-
tern. If this is the case, voltages are used for phase selection. The voltage algorithm is the same as the current-based algo-
rithm; for example, phase angles between the zero-sequence, negative-sequence, and positive-sequence voltages are
used. The pre-fault values are subtracted prior to any calculations.
The pre-fault quantities are captured and the calculations start when the disturbance detector (50DD) operates. When an
open pole is declared, the phase selector resets all its outputs operands and ignores any subsequent operations of the dis-
turbance detector.
The phase selector runs continuously. When there is no disturbance in the power system, and the disturbance detector
(50DD) from the source assigned as the
DISTANCE SOURCE
is reset, then the
PHASE SELECT VOID
FlexLogic operand is set
and all other phase selector operands are reset. All current and voltage sequence components are memorized and contin-
uously updated.
When the disturbance detector (50DD) operates, memory stops being updated and retains two cycles of old current and
voltage values. First, purely fault components of current and voltage are calculated by removing the pre-fault (memory)
quantities from presently calculated values. A series of conditions are checked with respect to magnitudes and phase
angles of current and voltage symmetrical components in order to detect the fault type. Secondly, currents are used to iden-
tify the fault type (AG, BG, CG, AB, BC, CA, ABG, BCG or CAG) according to the
Phase selection principle
figure above. If
the currents fail to identify the fault type, and voltages are available, then voltages are used. If any of the above types is
determined, then the corresponding FlexLogic operand below is asserted.
837725A1.CDR
AB,
ABG
CA,
CAG
BC,
BCG
AG
AG,
BCG
I
2F
I
2F
I
1F
I
0F
BG
CG,
ABG
CG
BG,
CAG
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...