GE Multilin
D60 Line Distance Protection System
5-311
5 SETTINGS
5.7 CONTROL ELEMENTS
5
f) OPEN POLE DETECTOR
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
OPEN POLE
The open pole detector is intended to identify an open pole of the line circuit breaker. The scheme monitors the breakers
auxiliary contacts, current in the circuit and optionally voltage on the line. The scheme generates output operands used to
block the phase selector and some specific protection elements, thus preventing maloperation during the dead time of a
single-pole autoreclose cycle or any other open pole conditions.
The scheme declares an open pole at the moment a single-pole trip is issued.
In two-breaker and breaker-and-a-half applications, an open pole condition is declared when one or more of the following
hold:
•
Both breakers have an open pole on the same phase.
•
The current on the line drops below a threshold.
•
The current and voltage on the line drop below a threshold.
The open pole feature uses signals defined by the
GROUPED ELEMENTS
SETTING GROUP 1(6)
DISTANCE
DISTANCE
SOURCE
setting. Voltage supervision can be used only with wye VTs on the line side of the breaker.
The
OPEN POLE CURRENT PICKUP
setting establishes the current threshold below which an open pole is declared.
The
OPEN POLE LINE XC1
setting specifies positive-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value is
entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay.
The
OPEN POLE LINE XC0
setting specifies zero-sequence reactance of the entire line. If shunt reactors are applied, this
value should be a net capacitive reactance of the line and the reactors installed between the line breakers. The value shall
be entered in secondary ohms. This setting is relevant if open pole condition at the remote end of the line is to be sensed
and utilized by the relay (
OPEN POLE REM OP
FlexLogic operand).
OPEN POLE
OPEN POLE FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
OPEN POLE BLOCK:
Off
Range: FlexLogic operand
MESSAGE
OPEN POLE VOLTAGE
SUPV: Disabled
Range: Disabled, Enabled
MESSAGE
OPEN POLE CURRENT
PKP: 0.050 pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
OPEN POLE LINE XC1:
9999.9
Ω
Range: 300.0 to 9999.9 ohms in steps of 0.001
MESSAGE
OPEN POLE LINE XC0:
9999.9
Ω
Range: 300.0 to 9999.9 ohms in steps of 0.001
MESSAGE
OPEN POLE REM CURR
PKP: 0.050 pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
OPEN POLE MODE:
Accelerated
Range: Accelerated, Traditional
MESSAGE
OPEN POLE DETECTION:
I AND V AND CBaux
Range: I AND V AND CBaux, I AND V only
MESSAGE
OPEN POLE TARGET:
Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
OPEN POLE EVENTS:
Disabled
Range: Enabled, Disabled
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...