GE Multilin
D60 Line Distance Protection System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
40E1
IEC 60870-5-104 Protocol Function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 Protocol Cyclic data Transmit Period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 Current Default Threshold
0 to 100000000
---
1
F003
30000
40E6
IEC 60870-5-104 Voltage Default Threshold
0 to 100000000
---
1
F003
30000
40E8
IEC 60870-5-104 Power Default Threshold
0 to 100000000
---
1
F003
30000
40EA
IEC 60870-5-104 Energy Default Threshold
0 to 100000000
---
1
F003
30000
40EC
IEC 60870-5-104 Power Default Threshold
0 to1
---
0.01
F001
100
40EE
IEC 60870-5-104 Other Default Threshold
0 to 100000000
---
1
F003
30000
40F0
IEC 60870-5-104 Client Address (5 items)
0 to 4294967295
---
1
F003
0
4104
IEC 60870-5-104 Redundancy Port
0 to 1
---
1
F126
0 (No)
4105
Port 2 IP Address
0 to 4294967295
---
1
F003
56554706
4107
Port 2 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4109
Port 2 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
410B
PRT2 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
410C
PRT2 Redundancy Enabled
0 to 2
---
1
F627
0 (None)
410D
Port 3 IP Address
0 to 4294967295
---
1
F003
56554706
410F
Port 3 IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
4111
Port 3 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
4113
Port 3 Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
4114
PRT1 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4115
PRT2 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4116
PRT3 GOOSE Enabled
0 to 1
---
1
F102
1 (Enabled)
4119
PRT2 PRP Mcst Addr
---
---
---
F072
0
411C
IEC Communications Reserved (33 items)
0 to 1
---
1
F001
0
413E
High Enet Traffic Function
0 to 1
---
1
F102
0 (Disabled)
413F
High Enet Traffic Events
0 to 1
---
1
F102
0 (Disabled)
4140
DNP Object 1 Default Variation
1 to 2
---
1
F001
2
4141
DNP Object 2 Default Variation
1 to 3
---
1
F001
2
4142
DNP Object 20 Default Variation
0 to 3
---
1
F523
0 (1)
4143
DNP Object 21 Default Variation
0 to 3
---
1
F524
0 (1)
4144
DNP Object 22 Default Variation
0 to 3
---
1
F523
0 (1)
4145
DNP Object 23 Default Variation
0 to 3
---
1
F523
0 (1)
4146
DNP Object 30 Default Variation
1 to 5
---
1
F001
1
4147
DNP Object 32 Default Variation
0 to 5
---
1
F525
0 (1)
4148
SCADA Protocol
0 to 2
---
1
F629
0 (DNP 3.0)
Communications Actuals (Read Only)
4160
Modbus Available TCP/IP Connections
0 to 4
---
1
F001
4
4161
DNP Available TCP/IP Connections
0 to 2
---
1
F001
2
4162
IEC Available TCP/IP Connections
0 to 2
---
1
F001
2
4163
MMS Available TCP/IP Connections
0 to 5
---
1
F001
5
4164
PMU Available TCP/IP Connections
0 to 4
---
1
F001
4
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) Server IP Address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP Port Number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (continuous)
4192
Data Logger Trigger
0 to 4294967295
---
1
F300
0
4194
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...