PORT 1 ... 3 PATH DELAY ADDER
•
The time delivered by PTP is advanced by the time value in this setting prior to the time being used to synchronize the
relay’s real time clock. This is to compensate to the extent practical for time delivery delays not compensated for in the
network. In a fully compliant PP network, the peer delay and the processing delay mechanisms compensate for all the
delays between the grandmaster and the relay. In such networks, this setting should be zero.
•
In networks containing one or more switches and/or clocks that do not implement both of these mechanisms, not all
delays are compensated, so the time of message arrival at the relay will be later than the time indicated in the mes-
sage. This setting can be used to approximately compensate for this delay. However, as the relay is not aware of net-
work switching that dynamically changes the amount of uncompensated delay, there is no setting that will always
completely correct for uncompensated delay. A setting can be chosen that will reduce worst-case error to half of the
range between minimum and maximum uncompensated delay, if these values are known.
PORT 1 ... 3 PATH DELAY ASYMMETRY
•
This setting corresponds to “delayAsymmetry” in PTP, which is used by the peer delay mechanism to compensate for
any difference in the propagation delay between the two directions of a link. Except in unusual cases, the two fibers are
of essentially identical length and composition, so this setting should be set to zero.
•
In unusual cases where the length of the link is different in different directions, this setting should be set to the number
of nanoseconds the Ethernet propagation delay to the relay is longer than the mean of path propagation delays to and
from the relay. For instance, if it is known say from the physical length of the fibers and the propagation speed in the
fibers that the delay from the relay to the Ethernet switch it is connected to is 9 000 ns and the that the delay from the
switch to the relay is 11 000 ns, then the mean delay is 10 000 ns, and the path delay asymmetry is 11000 - 10000 =
+1000 ns.
c) SNTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
SNTP PROTOCOL
The D60 supports the Simple Network Time Protocol specified in RFC-2030. With SNTP, the D60 can obtain clock time
over an Ethernet network. The D60 acts as an SNTP client to receive time values from an SNTP/NTP server, usually a ded-
icated product using a GPS receiver to provide an accurate time. Unicast SNTP is supported. The UR-series relays do not
support the broadcast, multicast or anycast SNTP functionality.
The
SNTP FUNCTION
setting enables or disabled the SNTP feature on the D60.
To use SNTP,
SNTP SERVER IP ADDR
must be set to the SNTP/NTP server IP address. Once this address is set and
SNTP
FUNCTION
is “Enabled”, the D60 attempts to obtain time values from the SNTP/NTP server. Since many time values are
obtained and averaged, it generally takes three to four minutes until the D60 clock is closely synchronized with the SNTP/
NTP server. It takes up to two minutes for the D60 to signal an SNTP self-test error if the server is offline.
The
SNTP UDP PORT NUMBER
is 123 for normal SNTP operation. If SNTP is not required, close the port by setting it to 0.
When the
SNTP UDP PORT NUMBER
is set to 0, the change takes effect when the D60 is restarted.
SNTP PROTOCOL
SNTP FUNCTION:
Disabled
Range: Enabled, Disabled
MESSAGE
SNTP SERVER IP ADDR:
0.0.0.0
Range: Standard IP address format
MESSAGE
SNTP UDP PORT
NUMBER: 123
Range: 0 to 65535 in steps of 1
NOTE
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...