GE Multilin
D60 Line Distance Protection System
5-331
5 SETTINGS
5.7 CONTROL ELEMENTS
5
f) HYBRID PERMISSIVE OVER-REACHING TRANSFER TRIP
PATH: SETTINGS
CONTROL ELEMENTS
PILOT SCHEMES
HYBRID POTT SCHEME
HYBRID POTT SCHEME
HYB POTT SCHEME
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
HYB POTT BLOCK:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT PERMISSIVE
ECHO: Disabled
Range: Disabled, Enabled, Custom
MESSAGE
HYB POTT ECHO COND:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT WEAK
INFEED: Enabled
Range: Disabled, Enabled, Custom
MESSAGE
HYB POTT W/I COND:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO DURATION:
0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
ECHO LOCKOUT:
0.250 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
HYB POTT SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
GND DIR O/C FWD:
Off
Range: FlexLogic operand
MESSAGE
GND DIR O/C REV:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT NO OF COMM
BITS: 1
Range: 1, 2, or 4
MESSAGE
HYB POTT RX1:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX2:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX3:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT RX4:
Off
Range: FlexLogic operand
MESSAGE
HYB POTT SCHEME
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
HYB POTT EVENT:
Disabled
Range: Disabled, Enabled
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...