9-4
D60 Line Distance Protection System
GE Multilin
9.2 DISTANCE ELEMENTS (STEPPED DISTANCE SCHEME)
9 APPLICATION OF SETTINGS
9
Figure 9–1: UNDERSTANDING SYSTEM HOMOGENEITY
If
, the zero-sequence network is more homogenous (the zero-sequence current better approximates
the fault current), and zero-sequence polarizing should be selected. Otherwise, negative-sequence is a better polarizing
signal.
The calculated
angles reflect errors between the ideal and applied polarizing angles. Therefore, after selecting the polar-
izing current, the corresponding angle should be chosen as the non-homogeneity correction angle. For example, calcula-
tions yielding
0
= 5° and
2
= –1° should result in selecting the negative-sequence for polarization, and the value of –1°
for non-homogeneity correction.
Quite often the non-homogeneity correction angle is used to apply extra security rather than correct the angle between the
relay and the fault currents. For extra security the angle should be set to negative values.
Ability to select an optimum polarizing signal and to correct for non-homogeneity should be approached with care. The best
polarizing signal and the correcting angle both depend on system parameters and intended reach of the zone. If the system
configuration is static, the selection is straightforward.
However, if the system configuration may change significantly, all the relevant system topologies shall be considered for
calculations. Either a compromise choice is made, or different settings are applied via switchable setting groups depending
on system conditions. In highly non-homogenous and dynamic systems where the correction for non-homogeneity is not
feasible, conservative reach (reduced) and/or correction angle (negative) settings should be considered.
c) GROUND DISTANCE ZONE 1
The zone 1 reach must be set so that nominally instantaneous operation does not extend beyond the end of the protected
line. However this may be somewhat more complicated than for the phase elements, because of zero sequence mutual
induction with an adjacent parallel line, possibly carried on the same tower, which can be out of service and grounded at
multiple points. A fault beyond 100% of the protected line may cause overreach unless the reach is reduced significantly,
sometimes as low as 65% of the line length. If the line being protected does not have a significant interaction with an adja-
cent circuit, then the typical 80% setting may be used. If there is significant mutual coupling between the parallel lines, then
the mutual compensation feature of the ground distance elements can be used instead of a drastic reduction in the reach.
However, even in this case, there is more uncertainty as compared with the phase distance elements because the zero-
sequence impedance of the line and thus the zero-sequence-compensating factors may vary significantly due to weather
and other conditions.
842742A1.CDR
dZ
dZ
(1 – d)Z
(1 – d)Z
Z
Z
0A
1A
0L
1L
0L
1L
Z
Z
0B
1B
I
I
I
I
I
0
2
2
0
F
I
I
F
F
DEPENDING ON SYSTEM
PARAMETERS, I0 OR I2 MAYBE A
BETTER APPROXIMATION OF THE
FAULT CURRENT ANGLE
abs
0
abs
2
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...