GE Multilin
D60 Line Distance Protection System
B-61
APPENDIX B
B.4 MEMORY MAPPING
B
A76C
...Repeated for Non-Volatile Latch 10
A778
...Repeated for Non-Volatile Latch 11
A784
...Repeated for Non-Volatile Latch 12
A790
...Repeated for Non-Volatile Latch 13
A79C
...Repeated for Non-Volatile Latch 14
A7A8
...Repeated for Non-Volatile Latch 15
A7B4
...Repeated for Non-Volatile Latch 16
Pilot POTT (1P) (Read/Write Setting)
A800
POTT 1P Scheme Function
0 to 1
---
1
F102
0 (Disabled)
A801
POTT 1P Permissive Echo
0 to 2
---
1
F199
0 (Disabled)
A802
POTT 1P Rx Pickup Delay
0 to 65.535
s
0.001
F001
0
A803
POTT 1P Trans Block Pickup Delay
0 to 65.535
s
0.001
F001
20
A804
POTT 1P Trans Block Reset Delay
0 to 65.535
s
0.001
F001
90
A805
POTT 1P Echo Duration
0 to 65.535
s
0.001
F001
100
A806
POTT 1P Echo Lockout
0 to 65.535
s
0.001
F001
250
A807
POTT 1P Line End Open Pickup Delay
0 to 65.535
s
0.001
F001
50
A808
POTT 1P Seal In Delay
0 to 65.535
s
0.001
F001
0
A809
POTT 1P Ground Directional Overcurrent Forward
0 to 4294967295
---
1
F300
0
A80B
POTT 1P Number of Communication Bits
0 to 2
---
1
F198
0 (1)
A80C
POTT 1P Rx1
0 to 4294967295
---
1
F300
0
A80E
POTT 1P Rx2
0 to 4294967295
---
1
F300
0
A810
POTT 1P Rx3
0 to 4294967295
---
1
F300
0
A812
POTT 1P Rx4
0 to 4294967295
---
1
F300
0
A814
POTT 1P Target
0 to 2
---
1
F109
0 (Self-reset)
A815
POTT 1P Event
0 to 1
---
1
F102
0 (Disabled)
A816
POTT 1P Echo Condition
0 to 4294967295
---
1
F300
0
A818
POTT 1P Scheme Block
0 to 4294967295
---
1
F300
0
A81A
Reserved (22 items)
0 to 1
---
1
F001
0
Pilot POTT1 (1P) (Read/Write Setting)
A830
POTT1 1P Scheme Function
0 to 1
---
1
F102
0 (Disabled)
A831
POTT1 1P Permissive Echo
0 to 2
---
1
F199
0 (Disabled)
A832
POTT1 1P Rx Pickup Delay
0 to 65.535
s
0.001
F001
0
A833
POTT1 1P Trans Block Pickup Delay
0 to 65.535
s
0.001
F001
20
A834
POTT1 1P Trans Block Reset Delay
0 to 65.535
s
0.001
F001
90
A835
POTT1 1P Echo Duration
0 to 65.535
s
0.001
F001
100
A836
POTT1 1P Echo Lockout
0 to 65.535
s
0.001
F001
250
A837
POTT1 1P Line End Open Pickup Delay
0 to 65.535
s
0.001
F001
50
A838
POTT1 1P Seal In Delay
0 to 65.535
s
0.001
F001
0
A839
POTT1 1P Ground Directional Overcurrent Forward
0 to 4294967295
---
1
F300
0
A83B
POTT1 1P Number of Communication Bits
0 to 2
---
1
F198
0 (1)
A83C
POTT1 1P Rx1
0 to 4294967295
---
1
F300
0
A83E
POTT1 1P Rx2
0 to 4294967295
---
1
F300
0
A840
POTT1 1P Rx3
0 to 4294967295
---
1
F300
0
A842
POTT1 1P Rx4
0 to 4294967295
---
1
F300
0
A844
POTT1 1P Target
0 to 2
---
1
F109
0 (Self-reset)
A845
POTT1 1P Event
0 to 1
---
1
F102
0 (Disabled)
A846
POTT1 1P Echo Condition
0 to 4294967295
---
1
F300
0
A848
POTT1 1P Scheme Block
0 to 4294967295
---
1
F300
0
A84A
POTT1 1P OC Fwd2
0 to 4294967295
---
1
F300
0
A84C
POTT1 1P OC Fwd2
0 to 4294967295
---
1
F300
0
A84E
Reserved (22 items)
0 to 1
---
1
F001
0
Pilot Blocking 1 (1P) (Read/Write Setting)
A864
Blocking 1 Scheme 1P Function
0 to 1
---
1
F102
0 (Disabled)
A865
Blocking 1 Scheme 1PBlock
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 53 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...