5-312
D60 Line Distance Protection System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
The
OPEN POLE REM CURR PKP
setting specifies pickup level for the remote-end current estimated by the relay as the local
current compensated by the calculated charging current. The latter is calculated based on the local voltages and the capac-
itive reactances of the line. This setting is relevant if open pole condition at the remote end of the line is to be sensed and
utilized by the relay (
OPEN POLE REM OP
FlexLogic operand).
The
OPEN POLE MODE
setting selects the mode of operation of the open pole function. When the “Accelerated” mode is cho-
sen, an open pole will be declared ½ cycle after trip output operation and before the breaker pole opens. This blocks dis-
tance loops involved in the faulted phase and phase selector, and arms the trip output to produce three-pole trip for the next
fault. If the fault evolves into multi-phase fault before breaker pole opens for the first fault, the remaining in-service distance
loops would initiate a three-pole trip. When the “Traditional” mode is selected, then an open pole is declared only after the
breaker opens and current disappears. If the fault evolves into a multi-phase fault before the circuit breaker pole opens for
the first fault, the phase selector will change the fault type from a single-line-to-ground fault to a multi-phase fault, thereby
initiating a three-pole trip.
The
OPEN POLE DETECTION
setting selects the signals used to detect an open pole condition. When “I AND V AND CBaux”
value is selected, the breaker 52 contacts and the current with optional voltage signals are used to determine open pole
conditions. For the “I AND V only” selection, only the current with optional voltage signals are used.
For convenience, the position of the breaker poles defined in the breaker control feature and available as FlexLogic oper-
and
BREAKER 1
Φ
A CLSD
through
BREAKER 1
Φ
C CLSD
and
BREAKER 1 OOS
are used by the open pole feature if the “I AND
V AND CBaux” detection value is selected.
For correct operation of the open pole detector, the breaker control, trip output, and single-pole autoreclose features must
be enabled and configured properly. When used in configuration with only one breaker, the
BREAKER 2 FUNCTION
should be
“Enabled” and the
BREAKER 2 OUT OF SV
setting should be “On” (refer to the
Breaker Control
section earlier in this chapter
for additional details).
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...