6 ACTUAL VALUES
6.2 STATUS
6
6.2.4 REMOTE DOUBLE-POINT STATUS INPUTS
PATH: ACTUAL VALUES
STATUS
REMOTE DPS INPUTS
The present state of the remote double-point status inputs is shown here. The actual values indicate if the remote double-
point status inputs are in the on (close), off (open), intermediate, or bad state.
6.2.5 TELEPROTECTION INPUTS
PATH: ACTUAL VALUES
STATUS
TELEPROTECTION INPUTS
The present state of teleprotection inputs from communication channels 1 and 2 are shown here. The state displayed will
be that of corresponding remote output unless the channel is declared failed.
6.2.6 CONTACT OUTPUTS
PATH: ACTUAL VALUES
STATUS
CONTACT OUTPUTS
The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact
output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of
the display indicates the logic state of the contact output.
REMOTE DPS INPUTS
REMOTE DPS INPUT 1
STATUS: Bad
Range: On, Off, Intermediate, Bad
MESSAGE
REMOTE DPS INPUT 2
STATUS: Bad
Range: On, Off, Intermediate, Bad
MESSAGE
REMOTE DPS INPUT 5
STATUS: Bad
Range: On, Off, Intermediate, Bad
TELEPROTECTION
INPUTS
TELEPROTECTION
INPUT 1-1: Off
Range: Off, On
MESSAGE
TELEPROTECTION
INPUT 1-2: Off
Range: Off, On
MESSAGE
TELEPROTECTION
INPUT 1-16: Off
Range: Off, On
MESSAGE
TELEPROTECTION
INPUT 2-1: Off
Range: Off, On
MESSAGE
TELEPROTECTION
INPUT 2-2: Off
Range: Off, On
MESSAGE
TELEPROTECTION
INPUT 2-16: Off
Range: Off, On
CONTACT OUTPUTS
Cont Op 1
Off
Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Cont Op 2
Off
Range: On, Off, VOff, VOn, IOn, IOff
MESSAGE
Cont Op xx
Off
Range: On, Off, VOff, VOn, IOn, IOff
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...