B-46
D60 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
68AB
DCUB Transmit Block Reset Delay
0 to 65.535
s
0.001
F001
90
68AC
Directional Comparison Unblocking Echo Duration
0 to 65.535
s
0.001
F001
100
68AD
Directional Comparison Unblocking Echo Lockout
0 to 65.535
s
0.001
F001
250
68AE
DCUB Line End Open Pickup Delay
0 to 65.535
s
0.001
F001
50
68AF
DCUB Loss-of-Guard Pickup Delay
0 to 65.535
s
0.001
F001
8
68B0
DCUB Guard Healthy Reset Delay
0 to 65.535
s
0.001
F001
15
68B1
DCUB Loss-of-Guard Trip Window
0 to 65.535
s
0.001
F001
150
68B2
Directional Comparison Unblocking Seal-In Delay
0 to 65.535
s
0.001
F001
10
68B3
Directional Comparison Unblocking Communication Bits
0 to 2
---
1
F198
0 (1 bit)
68B4
Directional Comparison Unblocking Rx1
0 to 4294967295
---
1
F300
0
68B6
Directional Comparison Unblocking LOG1
0 to 4294967295
---
1
F300
0
68B8
Directional Comparison Unblocking Rx2
0 to 4294967295
---
1
F300
0
68BA
Directional Comparison Unblocking LOG2
0 to 4294967295
---
1
F300
0
68BC
Directional Comparison Unblocking Rx3
0 to 4294967295
---
1
F300
0
68BE
Directional Comparison Unblocking LOG3
0 to 4294967295
---
1
F300
0
68C0
Directional Comparison Unblocking Rx4
0 to 4294967295
---
1
F300
0
68C2
Directional Comparison Unblocking LOG4
0 to 4294967295
---
1
F300
0
68C4
Directional Comparison Unblocking Target
0 to 2
---
1
F109
0 (Self-Reset)
68C5
Directional Comparison Unblocking Event
0 to 1
--
1
F102
0 (Disabled)
68C6
Reserved (6 items)
0 to 1
--
1
F001
0
Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)
7000
Phase Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7001
Phase Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7002
Phase Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7003
Phase Undervoltage 1 Curve
0 to 1
---
1
F111
0 (Definite Time)
7004
Phase Undervoltage 1 Delay
0 to 600
s
0.01
F001
100
7005
Phase Undervoltage 1 Minimum Voltage
0 to 3
pu
0.001
F001
100
7006
Phase Undervoltage 1 Block
0 to 4294967295
---
1
F300
0
7008
Phase Undervoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7009
Phase Undervoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
700A
Phase Undervoltage 1 Measurement Mode
0 to 1
---
1
F186
0 (Phase to
Ground)
700B
Reserved (6 items)
0 to 1
---
1
F001
0
7011
...Repeated for Phase Undervoltage 2
7022
...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
7040
Phase Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7041
Phase Overvoltage 1 Source
0 to 5
---
1
F167
0 (SRC 1)
7042
Phase Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
1000
7043
Phase Overvoltage 1 Delay
0 to 600
s
0.01
F001
100
7044
Phase Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7045
Phase Overvoltage 1 Block
0 to 4294967295
---
1
F300
0
7047
Phase Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7048
Phase Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7049
...Repeated for Phase Overvoltage 2
7052
...Repeated for Phase Overvoltage 3
Phase Distance (Read/Write Grouped Setting) (5 Modules)
7070
Phase Distance Zone 1 Function
0 to 1
---
1
F102
0 (Disabled)
7071
Phase Distance Zone 1 Current Supervision
0.05 to 30
pu
0.001
F001
200
7072
Phase Distance Zone 1 Reach
0.02 to 500
ohms
0.01
F001
200
7073
Phase Distance Zone 1 Direction
0 to 2
---
1
F154
0 (Forward)
7074
Phase Distance Zone 1 Comparator Limit
30 to 90
degrees
1
F001
90
7075
Phase Distance Zone 1 Delay
0 to 65.535
s
0.001
F001
0
7076
Phase Distance Zone 1 Block
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 38 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...