GE Multilin
D60 Line Distance Protection System
5-37
5 SETTINGS
5.2 PRODUCT SETUP
5
j) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
DNP PROTOCOL
DNP CHANNELS
Range: see sub-menu below
MESSAGE
DNP ADDRESS:
1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP NETWORK
CLIENT ADDRESSES
Range: see sub-menu below
MESSAGE
DNP TCP/UDP PORT
NUMBER: 20000
Range: 0 to 65535 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
DNP UNSOL RESPONSE
TIMEOUT: 5 s
Range: 0 to 60 s in steps of 1
MESSAGE
DNP UNSOL RESPONSE
MAX RETRIES: 10
Range: 1 to 255 in steps of 1
MESSAGE
DNP UNSOL RESPONSE
DEST ADDRESS: 1
Range: 0 to 65519 in steps of 1
MESSAGE
DNP CURRENT SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP VOLTAGE SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP POWER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP ENERGY SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP PF SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP OTHER SCALE
FACTOR: 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
MESSAGE
DNP CURRENT DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP VOLTAGE DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP POWER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP ENERGY DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP PF DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP OTHER DEFAULT
DEADBAND: 30000
Range: 0 to 100000000 in steps of 1
MESSAGE
DNP TIME SYNC IIN
PERIOD: 1440 min
Range: 1 to 10080 min. in steps of 1
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...