5-86
D60 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.14 FLEX STATE PARAMETERS
PATH: SETTINGS
PRODUCT SETUP
FLEX STATE PARAMETERS
This feature provides a mechanism where any of 256 selected FlexLogic operand states can be used for efficient monitor-
ing. The feature allows user-customized access to the FlexLogic operand states in the relay. The state bits are packed so
that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which
are of interest to the user are available in a minimum number of Modbus registers.
The state bits may be read out in the “Flex States” register array beginning at Modbus address 0900h. Sixteen states are
packed into each register, with the lowest-numbered state in the lowest-order bit. There are sixteen registers to accommo-
date the 256 state bits.
5.2.15 USER-DEFINABLE DISPLAYS
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
USER-DEFINABLE DISPLAYS
This menu provides a mechanism for manually creating up to 16 user-defined information displays in a convenient viewing
sequence in the
USER DISPLAYS
menu (between the
TARGETS
and
ACTUAL VALUES
top-level menus). The sub-menus facili-
tate text entry and Modbus register data pointer options for defining the user display content.
Once programmed, the user-definable displays can be viewed in two ways.
•
KEYPAD
: Use the MENU key to select the
USER DISPLAYS
menu item to access the first user-definable display (note
that only the programmed screens are displayed). The screens can be scrolled using the UP and DOWN keys. The
display disappears after the default message time-out period specified by the
PRODUCT SETUP
DISPLAY PROPER-
TIES
DEFAULT MESSAGE TIMEOUT
setting.
•
USER-PROGRAMMABLE CONTROL INPUT
: The user-definable displays also respond to the
INVOKE AND SCROLL
setting. Any FlexLogic operand (in particular, the user-programmable pushbutton operands), can be used to navigate
the programmed displays.
FLEX STATE
PARAMETERS
PARAMETER 1:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 2:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 3:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 256:
Off
Range: FlexLogic operand
USER-DEFINABLE
DISPLAYS
INVOKE AND SCROLL:
Off
Range: FlexLogic operand
MESSAGE
USER DISPLAY 1
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 3
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 2
Range: up to 20 alphanumeric characters
MESSAGE
USER DISPLAY 16
Range: up to 20 alphanumeric characters
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...