GE Multilin
D60 Line Distance Protection System
5-111
5 SETTINGS
5.4 SYSTEM SETUP
5
The switch element has direct hard-coded connections to IEC 61850 model as shown in the logic diagram. This allows
remote open/close operation of each switch, using either CSWI or XSWI IEC 61850 logical nodes. IEC 61850 select-
before-operate functionality, local/remote switch functionality along with a blocking open/close commands are provided.
Note that IEC 61850 commands are event-driven and dwell time for these is one protection pass only. If you want to main-
tain close/open command for a certain time, do so either on the contact outputs using the "Seal-in" setting or in FlexLogic.
5.4.6 FLEXCURVES
a) SETTINGS
PATH: SETTINGS
SYSTEM SETUP
FLEXCURVES
FLEXCURVE A(D)
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a
custom FlexCurve, enter the reset and operate times (using the VALUE keys) for each selected pickup point (using the
MESSAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
FLEXCURVE A
FLEXCURVE A TIME AT
0.00 xPKP:
0 ms
Range: 0 to 65535 ms in steps of 1
Table 5–12: FLEXCURVE TABLE
RESET
TIME
MS
RESET
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
OPERATE
TIME
MS
0.00
0.68
1.03
2.9
4.9
10.5
0.05
0.70
1.05
3.0
5.0
11.0
0.10
0.72
1.1
3.1
5.1
11.5
0.15
0.74
1.2
3.2
5.2
12.0
0.20
0.76
1.3
3.3
5.3
12.5
0.25
0.78
1.4
3.4
5.4
13.0
0.30
0.80
1.5
3.5
5.5
13.5
0.35
0.82
1.6
3.6
5.6
14.0
0.40
0.84
1.7
3.7
5.7
14.5
0.45
0.86
1.8
3.8
5.8
15.0
0.48
0.88
1.9
3.9
5.9
15.5
0.50
0.90
2.0
4.0
6.0
16.0
0.52
0.91
2.1
4.1
6.5
16.5
0.54
0.92
2.2
4.2
7.0
17.0
0.56
0.93
2.3
4.3
7.5
17.5
0.58
0.94
2.4
4.4
8.0
18.0
0.60
0.95
2.5
4.5
8.5
18.5
0.62
0.96
2.6
4.6
9.0
19.0
0.64
0.97
2.7
4.7
9.5
19.5
0.66
0.98
2.8
4.8
10.0
20.0
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...