GE Multilin
D60 Line Distance Protection System
5-205
5 SETTINGS
5.6 GROUPED ELEMENTS
5
I2t CURVES:
The curves for the I
2
t are derived from the formulae:
,
(EQ 5.10)
where:
T
= Operate Time (sec.); TDM = Multiplier Setting;
I
= Input Current;
I
pickup
= Pickup Current Setting;
T
RESET
= Reset Time in sec. (assuming energy capacity is 100% and RESET: Timed)
FLEXCURVES:
The custom FlexCurves are described in detail in the FlexCurves section of this chapter. The curve shapes for the Flex-
Curves are derived from the formulae:
(EQ 5.11)
(EQ 5.12)
where:
T
= Operate Time (sec.), TDM = Multiplier setting
I
= Input Current,
I
pickup
= Pickup Current setting
T
RESET
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
DEFINITE TIME CURVE:
The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from instanta-
neous to 600.00 seconds in steps of 10 ms.
(EQ 5.13)
(EQ 5.14)
where:
T
= Operate Time (sec.), TDM = Multiplier setting
I
= Input Current,
I
pickup
= Pickup Current setting
T
RESET
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
RECLOSER CURVES:
The D60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurve section in this
chapter for details.
Table 5–28: I
2
T CURVE TRIP TIMES
MULTIPLIER
(TDM)
CURRENT (
I
/
I
pickup
)
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
0.01
0.44
0.25
0.11
0.06
0.04
0.03
0.02
0.02
0.01
0.01
0.10
4.44
2.50
1.11
0.63
0.40
0.28
0.20
0.16
0.12
0.10
1.00
44.44
25.00
11.11
6.25
4.00
2.78
2.04
1.56
1.23
1.00
10.00
444.44
250.00
111.11
62.50
40.00
27.78
20.41
15.63
12.35
10.00
100.00
4444.4
2500.0
1111.1
625.00
400.00
277.78
204.08
156.25
123.46
100.00
600.00
26666.7
15000.0
6666.7
3750.0
2400.0
1666.7
1224.5
937.50
740.74
600.00
T
TDM
100
I
I
pickup
----------------
2
--------------------------
=
T
RESET
TDM
100
I
I
pickup
----------------
2
–
----------------------------
=
T
TDM
FlexCurve Time at
I
I
pickup
----------------
=
when
I
I
pickup
----------------
1.00
T
RESET
TDM
FlexCurve Time at
I
I
pickup
----------------
when
I
I
pickup
----------------
0.98
=
T
TDM in seconds, when
I I
pickup
=
T
RESET
TDM in seconds
=
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...