B-84
D60 Line Distance Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
EA23
PMU 1 Recording Force Trigger
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit Recording (Read/Write Setting)
EA2E
PMU 1 Record Function
0 to 1
---
1
F102
0 (Disabled)
EA2F
PMU 1 No Of Timed Records
2 to 128
---
1
F001
10
EA30
PMU 1 Trigger Mode Ex
0 to 1
---
1
F542
0 (Auto
Overwrite)
EA31
.PMU 1 Timed Trigger Position
1 to 50
%
1
F001
10
Phasor Measurement Unit Recording Ex (Read/Write Setting)
Phasor Measurement Unit Triggering (Read/Write Setting)
EA4A
PMU 1 User Trigger
0 to 4294967295
---
1
F300
0
Phasor Measurement Unit Voltage Trigger (Read/Write Setting)
EA56
PMU 1 Volt Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EA57
PMU 1 Voltage Trigger Low Volt
0.25 to 1.25
pu
0.001
F001
800
EA58
PMU 1 Voltage Trigger High Volt
0.75 to 1.75
pu
0.001
F001
1200
EA59
PMU 1 Voltage Trigger Pkp Time
0 to 600
s
0.01
F001
10
EA5A
PMU 1 Voltage Trigger Dpo Time
0 to 600
s
0.01
F001
100
EA5B
PMU 1 Voltage Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EA61
PMU 1 Voltage Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EA62
PMU 1 Voltage Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Current Trigger (Read/Write Setting
EAA4
PMU 1 Current Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EAA5
PMU 1 Current Trigger Pickup
0.1 to 30
pu
0.001
F001
1800
EAA6
PMU 1 Current Trigger Pkp Time
0 to 600
s
0.01
F001
10
EAA7
PMU 1 Current Trigger Dpo Time
0 to 600
s
0.01
F001
100
EAA8
PMU 1 Current Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EAAE
PMU 1 Current Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EAAF
PMU 1 Current Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
EAEC
PMU 1 Frequency Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EAED
PMU 1 Frequency Trigger Low Frequency
20 to 70
Hz
0.01
F001
4900
EAEE
PMU 1 Frequency Trigger High Frequency
20 to 70
Hz
0.01
F001
6100
EAEF
PMU 1 Frequency Trigger Pickup Time
0 to 600
s
0.01
F001
10
EAF0
PMU 1 Frequency Trigger Dropout Time
0 to 600
s
0.01
F001
100
EAF1
PMU 1 Frequency Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EAF7
PMU 1 Frequency Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EAF8
PMU 1 Frequency Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EB3A
PMU 1 df/dt Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB3B
PMU 1 df/dt Trigger Raise
0.1 to 15
Hz/s
0.01
F001
25
EB3C
PMU 1 df/dt Trigger Fall
0.1 to 15
Hz/s
0.01
F001
25
EB3D
PMU 1 df/dt Trigger Pkp Time
0 to 600
s
0.01
F001
10
EB3E
PMU 1 df/dt Trigger Dpo Time
0 to 600
s
0.01
F001
100
EB3F
PMU 1 df/dt Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EB45
PMU 1 df/dt Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB46
PMU 1 df/dt Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB88
PMU 1 Power Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB89
PMU 1 Power Trigger Active
0.25 to 3
pu
0.01
F001
1250
EB8A
PMU 1 Power Trigger Reactive
0.25 to 3
pu
0.01
F001
1250
EB8B
PMU 1 Power Trigger Apparent
0.25 to 3
pu
0.01
F001
1250
EB8C
PMU 1 Power Trigger Pkp Time
0 to 600
s
0.01
F001
10
EB8D
PMU 1 Power Trigger Dpo Time
0 to 600
s
0.01
F001
100
EB8E
PMU 1 Power Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EB94
PMU 1 Power Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
Table B–10: MODBUS MEMORY MAP (Sheet 76 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...