GE Multilin
D60 Line Distance Protection System
5-139
5 SETTINGS
5.4 SYSTEM SETUP
5
IEC 61850-90-5 AGGREGATOR 1 CONFIGURATION
•
PMU AGGREGATOR1: NAME:
A user-defined visible string of characters (max. 56) to identify the source of the
stream. This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the
IEC 61850 MSVID filed in the output stream.
•
AGGREGATOR1: PHYSICAL PORT:
This setting determines the physical ports through which the synchrophasor traf-
fic is transmitted. The range is 1, 2, 3.
•
PMU AGGREGATOR1: UDP:
This setting selects the UDP port number that is used by this dataset for network report-
ing. A default setting value for IEC 6150-90-5 is provided.
•
PMU AGGREGATOR1: NUMBER OF ASDUs:
This setting sets the number of Application Service Data Units
(ASDUs) from 1 through to 4.
m) CONTROL BLOCKS
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
IEC 90 – 5 MSVCB01 CONFIGURATION
as above
AGTR2 PDC CNTRL 1
Phasor data concentrator asserts control bit 1 as
received via the network
as above
AGTR2 PDC CNTRL 2
Phasor data concentrator asserts control bit 2 as
received via the network
as above
AGTR2 PDC CNTRL 3
Phasor data concentrator asserts control bit 3 as
received via the network.
as above
AGTR1 PDC CNTRL 16
Phasor data concentrator asserts control bit 16, as
received via the network.
Table 5–15: NUMBER OF ASDU
SETTINGS FOR ASDU TRANSMISSION
1
ASDU at T0 (current values)
2
ASDU at T-1 (previous values) + ASDU at T0 (current values)
3
ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) +
ASDU at T0 (current values)
IEC 90-5 MSVCB
CONFIGURATION
MSVCB 1 SVENA:
OFF
Range: FlexLogic operand
MESSAGE
MSVCB 1 CLIENT CTRL:
OFF
Range: FlexLogic operand
MESSAGE
MSVCB 1 SVENA DEFLT:
OFF
Range: FlexLogic operand
MESSAGE
MSVCB 1 CONFREV:
1
Range: 1 to 4294967295
MESSAGE
MSVCB 1 PRIORITY:
4
Range: 0 to 7
MESSAGE
MSVCB 1 IP CLASS:
46
Range: 0 to 252
MESSAGE
MSVCB 1 VID:
0
Range: 0 to 4095
MESSAGE
MSVCB 1 APPID:
0
Range: 0 to 16383
Table 5–14: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...