8-14
D60 Line Distance Protection System
GE Multilin
8.2 PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
8 THEORY OF OPERATION
8
Equations from the “Current Transformation” and “Voltage Transformation” columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11 trans-
former, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT loca-
tion setting for that zone shall be set to Dy11 and the relay would use
instead of a traditional
for the AB
phase distance element.
The current supervision pickup setting applies to the currents specified in the “Current Transformation” columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For more information on set-
tings please refer to Chapter 9: Application of Settings.
8.2.2 EXAMPLE
Consider the system shown below:
Figure 8–5: SAMPLE SYSTEM CONFIGURATION
Normally, in order to respond to the fault shown in the figure, a distance relay shall be applied at the relaying point X. The
relay input signals at this location are shown in the following table.
If installed at the location X, the relay would use the following input signals for its phase AB distance element:
V
=
V
AB
= 77.402 kV
57.5° primary or 29.49 V
57.5° secondary
I
=
I
A
–
I
B
= 2.576 kA
–27.6° primary or 42.93 A
–27.6° secondary
And consequently it would see an apparent impedance of:
Z
app
=
V
/
I
= 30.05
85° primary or 0.687
85° secondary
INPUT
PRIMARY
SECONDARY
VA
100.4 kV
–7.32°
38.25 V
–7.32°
VB
97.23 kV
–53.4°
37.04 V
–53.4°
VC
181.8 kV
–150.0°
69.26 V
–150.0°
IA
1.288 kA
–27.6°
21.47 A
–27.6°
IB
1.288 kA
152.4°
21.47 A
152.4°
IC
0
0
3
I
B
–
I
A
I
B
–
837727A2.CDR
AB
wye, 330 lag
°
0.688
85°
Ω∠
2.57
Ω∠
88.4°
150 MVA, 10%
13.8kV/315kV
Z = 30.11
85°
L
Ω∠
VT = 315kV/120V
CT = 300:5
VT = 13.8kV/120V
CT = 8000:5
delta
H
X
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...