Figure 5–86: GROUND DIRECTIONAL SUPERVISION SCHEME LOGIC
5.6.5 POWER SWING DETECT
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SW I2 SUPV ENAB:
Off
Range: FlexLogic operand
MESSAGE
POWER SWING
I2 SUPV: 0.2 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
V_0 > 5 volts
RUN
Zero-sequence
directional characteristic
837009A7.CDR
AND
OR
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle
SETTING
= V_0
= I_0
Distance Source
FLEXLOGIC OPERAND
OPEN POLE OP
TIMER
t
pickup
t
reset
FLEXLOGIC OPERAND
GND DIST Z2 DIR SUPN
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...