B.4 MEMORY MAPPING
B
B08D
IEC 61850 LPHD Location
0 to 65534
---
---
F204
“Location”
B0B5
Include non-IEC 61850 Data
0 to 1
---
1
F102
0 (Disabled)
B0B6
IEC 61850 Server Data Scanning Function
0 to 1
---
1
F102
0 (Disabled)
B0B7
IEC 61850 LPHD Latitude
-90 to 90
degree
0.001
F004
0
B0B9
IEC 61850 LPHD DC PhyNam Longitude
-180 to 180
degree
0.001
F004
0
B9BB
IEC 61850 LPHD DC PhyNam Altitude
0 to 10000
m
1
F003
0
B0BD
Reserved (3 items)
0 to 1
---
1
F001
0
IEC 61850 MMXU Deadbands (Read/Write Setting) (6 Modules)
B0C0
IEC 61850 MMXU TotW Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C2
IEC 61850 MMXU TotVAr Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C4
IEC 61850 MMXU TotVA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C6
IEC 61850 MMXU TotPF Deadband 1
0.001 to 100
%
0.001
F003
10000
B0C8
IEC 61850 MMXU Hz Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CA
IEC 61850 MMXU PPV.phsAB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CC
IEC 61850 MMXU PPV.phsBC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0CE
IEC 61850 MMXU PPV.phsCA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D0
IEC 61850 MMXU PhV.phsADeadband 1
0.001 to 100
%
0.001
F003
10000
B0D2
IEC 61850 MMXU PhV.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D4
IEC 61850 MMXU PhV.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D6
IEC 61850 MMXU A.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0D8
IEC 61850 MMXU A.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DA
IEC 61850 MMXU A.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DC
IEC 61850 MMXU A.neut Deadband 1
0.001 to 100
%
0.001
F003
10000
B0DE
IEC 61850 MMXU W.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E0
IEC 61850 MMXU W.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E2
IEC 61850 MMXU W.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E4
IEC 61850 MMXU VAr.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E6
IEC 61850 MMXU VAr.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0E8
IEC 61850 MMXU VAr.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EA
IEC 61850 MMXU VA.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EC
IEC 61850 MMXU VA.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0EE
IEC 61850 MMXU VA.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F0
IEC 61850 MMXU PF.phsA Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F2
IEC 61850 MMXU PF.phsB Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F4
IEC 61850 MMXU PF.phsC Deadband 1
0.001 to 100
%
0.001
F003
10000
B0F6
...Repeated for Deadband 2
B12C
...Repeated for Deadband 3
B162
...Repeated for Deadband 4
B198
...Repeated for Deadband 5
B1CE
...Repeated for Deadband 6
IEC 61850 Received Analogs (Read Only) (32 Modules)
B210
IEC 61850 Received Analog 1
-1000000000000 to
1000000000000
---
0.001
F060
0
B212
...Repeated for Received Analog 2
B214
...Repeated for Received Analog 3
B216
...Repeated for Received Analog 4
B218
...Repeated for Received Analog 5
B21A
...Repeated for Received Analog 6
B21C
...Repeated for Received Analog 7
B21E
...Repeated for Received Analog 8
B220
...Repeated for Received Analog 9
B222
...Repeated for Received Analog 10
B224
...Repeated for Received Analog 11
B226
...Repeated for Received Analog 12
Table B–10: MODBUS MEMORY MAP (Sheet 57 of 77)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...