5-82
D60 Line Distance Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
The local and remote operation of each user-programmable pushbutton can be inhibited through the
PUSHBTN 1 LOCAL
and
PUSHBTN 1 REMOTE
settings, respectively. If local locking is applied, the pushbutton will ignore set and reset commands
executed through the front panel pushbuttons. If remote locking is applied, the pushbutton will ignore set and reset com-
mands executed through FlexLogic operands.
The locking functions are not applied to the autorestart feature. In this case, the inhibit function can be used in SBO control
operations to prevent the pushbutton function from being activated and ensuring “one-at-a-time” select operation.
The locking functions can also be used to prevent the accidental pressing of the front panel pushbuttons. The separate
inhibit of the local and remote operation simplifies the implementation of local/remote control supervision.
Pushbutton states can be logged by the event recorder and displayed as target messages. In latched mode, user-defined
messages can also be associated with each pushbutton and displayed when the pushbutton is on or changing to off.
•
PUSHBUTTON 1 FUNCTION
: This setting selects the characteristic of the pushbutton. If set to “Disabled”, the push-
button is not active and the corresponding FlexLogic operands (both “On” and “Off”) are de-asserted. If set to “Self-
Reset”, the control logic is activated by the pulse (longer than 100 ms) issued when the pushbutton is being physically
pressed or virtually pressed via a FlexLogic operand assigned to the
PUSHBTN 1 SET
setting.
When in “Self-Reset” mode and activated locally, the pushbutton control logic asserts the “On” corresponding Flex-
Logic operand as long as the pushbutton is being physically pressed, and after being released the deactivation of the
operand is delayed by the drop out timer. The “Off” operand is asserted when the pushbutton element is deactivated. If
the pushbutton is activated remotely, the control logic of the pushbutton asserts the corresponding “On” FlexLogic
operand only for the time period specified by the
PUSHBTN 1 DROP-OUT TIME
setting.
If set to “Latched”, the control logic alternates the state of the corresponding FlexLogic operand between “On” and “Off”
on each button press or by virtually activating the pushbutton (assigning set and reset operands). When in the
“Latched” mode, the states of the FlexLogic operands are stored in a non-volatile memory. Should the power supply be
lost, the correct state of the pushbutton is retained upon subsequent power up of the relay.
•
PUSHBTN 1 ID TEXT:
This setting specifies the top 20-character line of the user-programmable message and is
intended to provide ID information of the pushbutton. See the
User-definable Displays
section for instructions on how
to enter alphanumeric characters from the keypad.
•
PUSHBTN 1 ON TEXT:
This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is in the “on” position. See the
User-definable Displays
section for instructions on
entering alphanumeric characters from the keypad.
•
PUSHBTN 1 OFF TEXT:
This setting specifies the bottom 20-character line of the user-programmable message and is
displayed when the pushbutton is activated from the on to the off position and the
PUSHBUTTON 1 FUNCTION
is
“Latched”. This message is not displayed when the
PUSHBUTTON 1 FUNCTION
is “Self-reset” as the pushbutton operand
status is implied to be “Off” upon its release. The length of the “Off” message is configured with the
PRODUCT SETUP
DISPLAY PROPERTIES
FLASH MESSAGE TIME
setting.
•
PUSHBTN 1 HOLD
: This setting specifies the time required for a pushbutton to be pressed before it is deemed active.
This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be
pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer.
•
PUSHBTN 1 SET
: This setting assigns the FlexLogic operand serving to operate the pushbutton element and to assert
PUSHBUTTON 1 ON
operand. The duration of the incoming set signal must be at least 100 ms.
•
PUSHBTN 1 RESET
: This setting assigns the FlexLogic operand serving to reset pushbutton element and to assert
PUSHBUTTON 1 OFF
operand. This setting is applicable only if pushbutton is in latched mode. The duration of the
incoming reset signal must be at least 50 ms.
•
PUSHBTN 1 AUTORST
: This setting enables the user-programmable pushbutton autoreset feature. This setting is
applicable only if the pushbutton is in the “Latched” mode.
•
PUSHBTN 1 AUTORST DELAY
: This setting specifies the time delay for automatic reset of the pushbutton when in
the latched mode.
•
PUSHBTN 1 REMOTE
: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the
operand assigned to the
PUSHBTN 1 SET
or
PUSHBTN 1 RESET
settings.
•
PUSHBTN 1 LOCAL
: This setting assigns the FlexLogic operand serving to inhibit pushbutton operation from the front
panel pushbuttons. This locking functionality is not applicable to pushbutton autoreset.
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...