5-148
D60 Line Distance Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
ELEMENT:
Neutral
instantaneous
overcurrent
NEUTRAL IOC1 PKP
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
NEUTRAL IOC2
Same set of operands as shown for NEUTRAL IOC1
ELEMENT:
Neutral overvoltage
NEUTRAL OV1 PKP
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has dropped out
Neutral overvoltage element 1 has operated
ELEMENT:
Neutral time
overcurrent
NEUTRAL TOC1 PKP
NEUTRAL TOC1 OP
NEUTRAL TOC1 DPO
Neutral time overcurrent 1 has picked up
Neutral time overcurrent 1 has operated
Neutral time overcurrent 1 has dropped out
NEUTRAL TOC2
Same set of operands as shown for NEUTRAL TOC1
ELEMENT:
Neutral directional
overcurrent
NTRL DIR OC1 FWD
NTRL DIR OC1 REV
Neutral directional overcurrent 1 forward has operated
Neutral directional overcurrent 1 reverse has operated
NTRL DIR OC2
Same set of operands as shown for NTRL DIR OC1
ELEMENT:
Open pole detector
OPEN POLE OP
Ф
A
OPEN POLE OP
Ф
B
OPEN POLE OP
Ф
C
OPEN POLE BKR
Ф
A OP
OPEN POLE BKR
Ф
B OP
OPEN POLE BKR
Ф
C OP
OPEN POLE BLK N
OPEN POLE BLK AB
OPEN POLE BLK BC
OPEN POLE BLK CA
OPEN POLE REM OP
Ф
A
OPEN POLE REM OP
Ф
B
OPEN POLE REM OP
Ф
C
OPEN POLE OP
OPEN POLE I<
Ф
A
OPEN POLE I<
Ф
B
OPEN POLE I<
Ф
C
Open pole condition is detected in phase A
Open pole condition is detected in phase B
Open pole condition is detected in phase C
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase A
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase B
Based on the breaker(s) auxiliary contacts, an open pole condition is
detected on phase C
Blocking signal for neutral, ground, and negative-sequence overcurrent
element is established
Blocking signal for the AB phase distance elements is established
Blocking signal for the BC phase distance elements is established
Blocking signal for the CA phase distance elements is established
Remote open pole condition detected in phase A
Remote open pole condition detected in phase B
Remote open pole condition detected in phase C
Open pole detector is operated
Open pole undercurrent condition is detected in phase A
Open pole undercurrent condition is detected in phase B
Open pole undercurrent condition is detected in phase C
ELEMENT:
Overfrequency
OVERFREQ 1 PKP
OVERFREQ 1 OP
OVERFREQ 1 DPO
Overfrequency 1 has picked up
Overfrequency 1 has operated
Overfrequency 1 has dropped out
OVERFREQ 2 to 4
Same set of operands as shown for OVERFREQ 1
ELEMENT:
Synchrophasor
phasor data
concentrator
PDC NETWORK CNTRL 1
PDC NETWORK CNTRL 2
PDC NETWORK CNTRL 16
Phasor data concentrator asserts control bit 1 as received via the network
Phasor data concentrator asserts control bit 2 as received via the network
Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT:
Phase directional
overcurrent
PH DIR1 BLK A
PH DIR1 BLK B
PH DIR1 BLK C
PH DIR1 BLK
Phase A directional 1 block
Phase B directional 1 block
Phase C directional 1 block
Phase directional 1 block
PH DIR2
Same set of operands as shown for PH DIR1
ELEMENT:
Phase distance
PH DIST Z1 PKP
PH DIST Z1 OP
PH DIST Z1 OP AB
PH DIST Z1 OP BC
PH DIST Z1 OP CA
PH DIST Z1 PKP AB
PH DIST Z1 PKP BC
PH DIST Z1 PKP CA
PH DIST Z1 SUPN IAB
PH DIST Z1 SUPN IBC
PH DIST Z1 SUPN ICA
PH DIST Z1 DPO AB
PH DIST Z1 DPO BC
PH DIST Z1 DPO CA
Phase distance zone 1 has picked up
Phase distance zone 1 has operated
Phase distance zone 1 phase AB has operated
Phase distance zone 1 phase BC has operated
Phase distance zone 1 phase CA has operated
Phase distance zone 1 phase AB has picked up
Phase distance zone 1 phase BC has picked up
Phase distance zone 1 phase CA has picked up
Phase distance zone 1 phase AB IOC is supervising
Phase distance zone 1 phase BC IOC is supervising
Phase distance zone 1 phase CA IOC is supervising
Phase distance zone 1 phase AB has dropped out
Phase distance zone 1 phase BC has dropped out
Phase distance zone 1 phase CA has dropped out
PH DIST Z2 to Z5
Same set of operands as shown for PH DIST Z1
Table 5–17: D60 FLEXLOGIC OPERANDS (Sheet 5 of 11)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...