GE Multilin
D60 Line Distance Protection System
8-19
8 THEORY OF OPERATION
8.4 SERIES COMPENSATED LINES
8
Figure 8–7: DYNAMIC REACH CONTROL
Section (a) of the figure below shows the effect of adaptive reach control for low-current external fault. The reach is reduced
sufficiently to cope with both transient and steady-state overreach. Section (b) shows a high-current external fault. The air
gaps or MOVs conduct majority of the fault current and neither steady-state nor transient overreach takes place. The relay
does not reduce its reach as it is not necessary. Section (c) shows a high-current internal fault. Because of the large cur-
rent, the reach is not reduced and the element responds to this internal fault. Traditional approach would leave this fault out
of the relay reach.
The neutral and negative-sequence directional protection functions of the relay cope with the voltage and/or current inver-
sions by adding appropriate offset to their polarizing signals as explained in the Ground Directional Overcurrent section.
The offset impedance can always be successfully selected to guarantee correct fault direction discrimination regardless of
the degree of compensation and location of the series capacitors and the potential source.
See Chapter 9: Application of Settings for detailed recommendations on settings for series compensation applications.
837729A1.CDR
THE REACH IS
DYNAMICALLY
REDUCED BY
V
L
/abs(I)
SET REACH (Z
R
)
ACTUAL REACH IS
A FUNCTION OF
CURRENT
MAGNITUDE
ACTUAL REACH
FOR VERY HIGH
CURRENTS
ACTUAL REACH
FOR VERY SMALL
CURRENTS
R
X
FAR-E
ND
BUSB
AR
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...