5 SETTINGS
5.7 CONTROL ELEMENTS
5
•
The breaker status is open.
•
An elevated high frequency current condition occurs and the current subsequently drops out again.
The algorithm is illustrated in the state machine diagram shown below.
Figure 5–157: ALGORITHM ILLUSTRATION – STATE MACHINE TO DETECT RESTRIKE
In this way, a distinction is made between a self-extinguishing restrike and permanent breaker failure condition. The latter
can be detected by the breaker failure function or a regular instantaneous overcurrent element. Also, a fast succession of
restrikes will be picked up by breaker failure or instantaneous overcurrent protection.
The following settings are available for each element.
•
BREAKER RESTRIKE 1 FUNCTION
: This setting enable and disables operation of the breaker restrike detection ele-
ment.
•
BRK RSTR 1 BLOCK
: This setting is used to block operation of the breaker restrike detection element.
•
BREAKER RESTRIKE 1 SOURCE
: This setting selects the source of the current for this element. This source must
have a valid CT bank assigned.
•
BREAKER RESTRIKE 1 PICKUP
: This setting specifies the pickup level of the overcurrent detector in per-unit values
of CT nominal current.
•
BREAKER RESTRIKE 1 RESET DELAY
: This setting specifies the reset delay for this element. When set to “0 ms”,
then FlexLogic operand will be picked up for only 1/8th of the power cycle.
•
BRK RSTR 1 BRK OPEN
: This setting assigns a FlexLogic operand indicating the open position of the breaker. It must
be logic “1” when breaker is open.
•
BRK RSTR 1 OPEN CMD
: This setting assigns a FlexLogic operand indicating a breaker open command. It must be
logic “1” when breaker is opened, either manually or from protection logic.
•
BRK RSTR 1 CLS CMD
: This setting assigns a FlexLogic operand indicating a breaker close command. It must be
logic “1” when breaker is closed.
Capacitor bank
offline
Current
interruption
(overcurrent)
High-frequency
elevated current
Restrike detected:
OP state asserted
Breaker close
Breaker
close
Breaker
close
Capacitor bank
online
Current
interruption
(overcurrent)
Breaker open
command or breaker
open state
834768A1.CDR
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...