8-4
D60 Line Distance Protection System
GE Multilin
8.1 DISTANCE ELEMENTS
8 THEORY OF OPERATION
8
The ground elements are polarized from either zero-sequence or negative-sequence current as per user-settings to maxi-
mize performance in non-homogenous systems. The polarizing current is additionally shifted by the user-selectable non-
homogeneity correction angle.
f) REVERSE QUADRILATERAL REACTANCE CHARACTERISTIC FOR NON-DIRECTIONAL APPLICATIONS
The reverse quadrilateral reactance characteristic is achieved by checking the angle between:
AB phase element:
(I
A
– I
B
)
Z
REV
– (V
A
– V
B
)
and
(I
A
– I
B
)
Z
REV
BC phase element:
(I
B
– I
C
)
Z
REV
– (V
B
– V
C
)
and
(I
B
– I
C
)
Z
REV
CA phase element:
(I
C
– I
A
)
Z
REV
– (V
C
– V
A
)
and
(I
C
– I
A
)
Z
REV
A ground element:
I
A
Z + I_0
K0
Z
REV
+ I
G
K0M
Z
REV
– V
A
and
(j
I_0 or j
I_2A)
e
j(180 +
)
B ground element:
I
B
Z + I_0
K0
Z
REV
+ I
G
K0M
Z
REV
– V
B
and
(j
I_0 or j
I_2B)
e
j(180 +
)
C ground element:
I
C
Z + I_0
K0
Z
REV
+ I
G
K0M
Z
REV
– V
C
and
(j
I_0 or j
I_2C)
e
j(180 +
)
The ground elements are polarized from either zero-sequence or negative-sequence current as per user-settings to maxi-
mize performance in non-homogenous systems. The polarizing current is additionally shifted by the user-selectable non-
homogeneity correction angle.
g) DIRECTIONAL CHARACTERISTIC
The directional characteristic is achieved by checking the angle between:
AB phase element:
(I
A
– I
B
)
Z
D
and
(V
A
– V
B
)_1M
BC phase element:
(I
B
– I
C
)
Z
D
and
(V
B
– V
C
)_1M
CA phase element:
(I
C
– I
A
)
Z
D
and
(V
C
– V
A
)_1M
A ground element:
I_0
Z
D
and
V
A
_1M
I
A
_2
Z
D
and
V
A
_1M
B ground element:
I_0
Z
D
and
V
B
_1M
I
B
_2
Z
D
and
V
B
_1M
C ground element:
I_0
Z
D
and
V
C
_1M
I
C
_2
Z
D
and
V
C
_1M
The characteristic and limit angles of the directional comparator are adjustable independently from the mho and reactance
comparators. The directional characteristic improves directional integrity of the distance functions.
h) RIGHT BLINDER
The right blinder characteristic is achieved by checking the angle between the following signals:
AB phase element:
(I
A
– I
B
)
Z
R
– (V
A
– V
B
)
and
(I
A
– I
B
)
Z
R
BC phase element:
(I
B
– I
C
)
Z
R
– (V
B
– V
C
)
and
(I
B
– I
C
)
Z
R
CA phase element:
(I
C
– I
A
)
Z
R
– (V
C
– V
A
)
and
(I
C
– I
A
)
Z
R
A ground element:
I
A
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
– V
A
and
I
A
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
B ground element:
I
B
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
– V
B
and
I
B
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
C ground element:
I
C
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
– V
C
and
I
C
Z
R
+ I_0
K0
Z
R
+ I
G
K0M
Z
R
The blinders apply to the Quad characteristic only.
i) LEFT BLINDER
The left blinder characteristic is achieved by checking the angle between the following signals:
AB phase element:
(I
A
– I
B
)
Z
L
– (V
A
– V
B
)
and
(I
A
– I
B
)
Z
L
BC phase element:
(I
B
– I
C
)
Z
L
– (V
B
– V
C
)
and
(I
B
– I
C
)
Z
L
CA phase element:
(I
C
– I
A
)
Z
L
– (V
C
– V
A
)
and
(I
C
– I
A
)
Z
L
A ground element:
I
A
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
– V
A
and
I
A
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
B ground element:
I
B
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
– V
B
and
I
B
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
C ground element:
I
C
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
– V
C
and
I
C
Z
L
+ I_0
K0
Z
L
+ I
G
K0M
Z
L
The blinders apply to the Quad characteristic only.
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...