GE Multilin
D60 Line Distance Protection System
5-127
5 SETTINGS
5.4 SYSTEM SETUP
5
PMU 1 STYLE
: This setting selects whether synchrophasors are reported in rectangular (real and imaginary) coordinates
or in polar (magnitude and angle) coordinates. This setting complies with bit-0 of the FORMAT field of the IEEE C37.118
configuration frame.
With 90-5 PMU, the FORMAT and STYLE are Floating-point and Polar respectively, as specified in the IEC 61850
standard.
IEC 61850–90–5 PMU 1 CONFIGURATION
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
BASIC CONFIGURATION
PMU1
PMU 1 BASIC CONFIGURA-
TION
90 – 5 PMU 1 CONFIGURATION
PMU1 LDINST
: A user-defined visible string (maximum 64 char ASCII test) to assign Logical Device (LD) Inst for a PMU
LD.
As per IEC 61850-6 standard specification, the PMU LD Name is the concatenated combination (to total 64 charac-
ters) of IED Name (specified in IEC 61850 Server Settings) appended with PMU X LDINST string.
90–5 PMU 1
CONFIGURATION
PMU 1 LDINST:
PMU1
Range: 64 char ASCII text
NOTE
NOTE
Содержание D60
Страница 61: ...GE Multilin D60 Line Distance Protection System 2 31 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Страница 62: ...2 32 D60 Line Distance Protection System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 102: ...3 40 D60 Line Distance Protection System GE Multilin 3 3 DIRECT INPUT AND OUTPUT COMMUNICATIONS 3 HARDWARE 3 ...
Страница 134: ...4 32 D60 Line Distance Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 508: ...5 374 D60 Line Distance Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 538: ...6 30 D60 Line Distance Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 610: ...10 8 D60 Line Distance Protection System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Страница 622: ...A 12 D60 Line Distance Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 745: ...GE Multilin D60 Line Distance Protection System B 123 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 746: ...B 124 D60 Line Distance Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 776: ...C 30 D60 Line Distance Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 792: ...E 10 D60 Line Distance Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Страница 804: ...F 12 D60 Line Distance Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 826: ...xii D60 Line Distance Protection System GE Multilin INDEX ...