D - 7
Appendix D
•
Vission 20/20 Communication Table
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Vilter
TM
Address
Ethernet
IP
Address
Modbus
Address
Command Name
Data
Type
Value
Mode
Lower
Range
Higher
Range
104
N55:10
40410
Current Run Mode
ENUM
"0 = Idle
1 = Waiting
2 = Starting
3 = Manual
4 = Auto (Internal Capacity
Control)
5 = Remote Auto (Internal
Capacity Control)
6 = Remote Load/Unload
7 = Remote Capacity Hold
%
8 = Remote Ready (Idle)
9 = Direct I/O Auto
Capacity
10 = Direct I/O Manual
Capacity
11 = Direct I/O Capacity
Hold %
12 = Auto Sequencing"
Read
105
N55:11
40411
Load Limiting Condition WORD
"Bit 0 = High Motor Amps
Bit 1 = High Discharge
Pressure
Bit 2 = Low Suction
Pressure
Bit 3 = High Discharge
Superheat
Bit 4 = Cool Compression
SOI
Bit 5 = Low Compression
Ratio"
Read
106
N55:12
40412
Oil Pump Status
INT
0 = OFF, 1 = ON
Read
107
N55:13
40413
Oil Pump Operation
ENUM
"0 = No Pump
1 = Stal
2 = Cycling
3 = Full Time
4 = Cool Compression
5 = Suction Oil Injection
Solenoid"
Read
108
N55:14
40414
Compressor Model
ENUM
"0 = VSR
1 = VSM
2 = VSS
3 = VRS
4 = VSM7"
Read
109
N55:15
40415
Refrigerant
ENUM
"0 = R12
1 = R22
2 = R134a
3 = R290
4 = R404a
5 = R502
6 = R507
7 = R717
8 = R744
9 = Natural Gas"
Read
110
N55:16
40416
Runtime Hours (x1000)
INT
Read
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......