10 – 15
Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 10-13. Compressor Setup for Compressor Sequencing (Slave)
Configuration Overview
NOTE
Slave Compressors should be configured first, and
then configure the Master Compressor.
The Configuration screen allows the operator to:
• Enable / Disable Compressor Sequencing
• Select Slave / Master Mode of operation for the
compressor
• Assign a unique compressor name
• Enable Ethernet port
• Select Modbus TCP protocol
• Assign a unique Ethernet IP address
SETTING UP THE SLAVE COMPRESSORS FOR
SEQUENCING
1. Log onto each of the slave compressors one by
one and navigate to the Configuration screen, see
Figure 10-13.
2. Enable the Ethernet port and select the Modbus
TCP protocol.
3. Set up a unique Ethernet IP address for each slave.
4. Set up the Subnet Mask for the IP address.
5. Set up the Gateway address (MUST DO!)
6. Enable the sequencing in slave mode.
7. Select a Network Name for sequencing.
8. Select a Unique Name for each slave compressor.
9. Set the Communications Active Remote Control to
“ETHERNET” for each slave compressor.
10. Apply these settings before exiting the
Configuration screen.