B - 41
Appendix B
•
Vission 20/20 Application Procedures
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
HARDWARE WIRING
Interconnect wiring between the Vission 20/20 panel
and the VPLUS panel now needs to be done.
1. First make sure that the VPLUS panel and the
Vission 20/20 panel control power comes from the
same source.
2. Next, the Vission 20/20 analog output card must
be wired to the Dart speed controller board. The
analog output that is used for this is AO#4, see
Figure B-30. Wires from AO#4 will land on wires
106 and 107, see Figure B-29.
3. Finally, the VPLUS relay (CRV) shown in Figure B-29
must also be wired to the Vission 20/20. This relay
will be controlled by the Vission 20/20 digital out-
put (board #2, output #5) – the liquid injection so-
lenoid output. Run a wire from terminal 25 in the
20/20 panel to terminal 104 in the VPLUS panel, see
Figure B-31.
Figure B-30. Analog Output Card Wiring to VPLUS Dart Speed Controller (Wire 106 and 107)