13 – 2
Section 13
•
Instruments Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Offset:
• Once the two point calibration is completed, it is not
uncommon for a small error to exist. By entering the
value of the error from the calibrated value and the
actual value into the adjustment entry box, that error
will be added/subtracted from the total offset. The
offset is applied to the calibrated value which should
correct the error.
Range:
• This option is available when the custom device op-
tion is chosen. Here the operator defines the signal
type and range transmitted by the instrument. The
operator can choose from several predefined ranges
in the drop-down box or enter a value.
Process Control Inputs
Page three of the Instrument Calibration screen is
dedicated to instruments used for Process Control; see
Figures 13-3 and 13-4.
The Process Control tab on this page will display ei-
ther Temperature or Pressure depending on the
selected control model. The tab is divided into two
sections, Device Calibration and Channel Calibration
with Default and Custom Devices as well as Offset and
Range Calibration features as described for the standard
Pressure and Temperature Inputs.
Motor Current
The Vission 20/20 has two options for measuring motor
current. A 4-20mA signal transmitted from an external
device or a 0-5Amp AC current Transformer. The type
of device being used is selected in the Configuration
Screen, an Motor Current Device in Section 19.
The motor current tab has the ability to calibrate both
measurement options through the 4-20mA scale and
current transformer ratio sections, see Figure 13-5.
Instruments Calibration Screen - Analog Inputs (Page
3). However, the type of device that is selected in the
configuration screen will be the only section available to
the operator.
The calibration differs from all other calibration proce-
dures in that the motor current must be calibrated while
the compressor is running at close to full load amps as
Figure 13-2. Instruments Calibration Screen - Analog Inputs (Page 2)
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......