26 – 2
Section 26
•
Remote Oil Cooler
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Manual
• Mode for controlling the Remote Oil Cooler opera-
tion manually. The operation is controlled by manual
stepping using an on/off toggle button at each step.
Remote Oil Cooler Temperature:
• This is a read-only parameter and it displays the pres-
ent value of the Remote Oil Cooler Temperature. The
Remote Oil Cooler Temperature is mapped on Analog
Auxiliary Input #5.
Remote Oil Cooler Temperature Setpoint:
• This is the Remote Oil Cooler Temperature setpoint
that needs to be maintained.
Upper Deadband:
• This is the Remote Oil Cooler Temperature setpoint’s
upper deadband value.
Lower Deadband:
• This is the Remote Oil Cooler Temperature setpoint ‘s
lower deadband value.
High to Low Speed Fan Delay:
• This is time delay for fan spin down in case of 2 speed
motor/dual speed fan.
Step Control
The Step Control allows the operator to setup the man-
ner in which Fans, Pumps & VFD will be turned on/off.
Fans & Pumps are connected on digital outputs Out
#1 to Out #4. The VFD Fan is connected to the Analog
Output. Each step can have a maximum of five outputs
connected to it. Each step can be opted in or out de-
pending an enabled checkbox.
When the Run Mode is “Auto” and the Remote Oil
Cooler Temperature rises above the upper deadband,
the Remote Oil Cooler step gets increased from Step 1
to Step 5, hence switching on/off Pumps, Fans & VFD
connected to outputs. This holds true when it comes
to decreasing the steps from Step 5 to Step 1 when the
Remote Oil Cooler Temperature falls below the lower
deadband.
Step Delay:
• Allows the operator to set time delays between
the Remote Oil Cooler steps. Remote Oil Cooler
Temperature must be outside the upper or lower
deadband continuously for the delay time in order
to increase or decrease the Remote Oil Cooler steps.
While in a VFD step, an additional step can only be
added once the VFD has reached its maximum speed
setpoint and the delay timers are satisfied. Similarly
in a VFD step, a step can only be removed once the
VFD has reached its minimum speed setpoint and the
delay timers are satisfied. The Step Delay acts as an
“ON” timer while loading and acts as an “OFF” timer
while unloading for the same step.
Low Speed Fan:
• Allows steps to have an option for time delay in case
of fan spin down. Any of Out #1 to Out #4 can be se-
lected as Low Speed Fan through combo box. E.g.:
Let’s say Out #2 is selected as Low Speed Fan in Step
2. When step 2 becomes active during Remote Oil
Cooler operation, which is after Step 2’s timeout de-
lay, Out #2 is left off for the time set by the operator
in High to Low Speed Delay. After the low speed fan
energizes, then the timer for Step 3 starts timing.
Control:
• Toggle any of the steps On/Off during the manual
operation of the Remote Oil Cooler. This button is ac-
tive only when the Run Mode selected is “Manual”.
During “Auto” operation of the Remote Oil Cooler
Control, the control button for the active step will be
“ON”.
VFD Settings
This page is active only when Remote Oil Cooler VFD is
selected in the Configuration Screen, see Section 19.
For the Remote Oil Cooler VFD Screen, see Figure 26-
2. When a VFD fan is used for the Remote Oil Cooler oil
cooling, the speed of the VFD is controlled using a PID
algorithm.
P = Proportional (gain):
• Used to adjust the fan speed action in direct propor-
tion to the difference between the control setpoint
and the process variable (SP - PV = error). The pro-
portional term is a unitless quantity and is used for
coarse adjustment. This setpoint should be set to the
lowest value that gives adequate control system re-
sponse. Increasing the proportional setting increases
the control system’s sensitivity to small process fluc
-
tuations and the tendency to hunt.
I = Integral (reset):
• Used to adjust the capacity control action, integrat-
ing the error over time, to account for a small error
that has persisted for a long time. This quantity is
used for fine adjustment. This setpoint is used to
smooth out process variations. This setpoint should
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......