14 – 5
Section 14
•
Slide Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 14-4. Photo-chopper
Press down on Photo-chopper to release tension from mo-
tor mount.
8. Use the “+” button on the Vission 20/20 to drive
the capacity slide to its maximum mechanical stop
position. This will be apparent by a slowing of the
motor rotation and a winding sound from the ac-
tuator motor. When you hear the motor wind-up,
release the “+” button.
9. Quickly press and release the BLUE CALIBRATION
BUTTON on the ACTUATOR motor once. The
RED LED will stop flashing. This now instructs the
ACTUATOR motor that this point is the maximum
slide position. This point corresponds to 5 volts. The
ACTUATOR calibration procedure is completed.
Now the Capacity Channel is automatically cali-
brated based on the calibration settings made to
the actuator.
CAUTION
Do not over tighten screws. Failure to comply
may result in damage to equipment.
10. Gently lower the plastic cover to where it contacts
the base and O-ring seal. After making sure that the
cover is not binding, gently tighten the four screws.
11. Repeat the same procedure for the Volume slide
motor.