10 – 8
Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
pressure control setpoint then this timer’s value is
used to make periodic sequencing decisions.
Fast Load Timer:
• If discharge pressure drops below the fast load pres-
sure offset setpoint then this timer’s value is used to
make periodic sequencing decisions.
Slow Unload Timer:
• If discharge pressure surpasses the discharge pres-
sure control setpoint then this timer’s value is used
to make periodic sequencing decisions.
Fast Unload Timer:
• If discharge pressure surpasses the fast unload pres-
sure offset setpoint then this timer’s value is used to
make periodic sequencing decisions.
Devices List
This screen is designed to add, display, delete and test
connection with slave compressors that are used by
the master compressor for sequencing. For Devices List
screen see Figure 10-6.
DEVICES LIST COLUMNS
Device Name:
• Displays the Name of the Slave Compressor.
Device Type:
• Displays the type of the Slave Compressor controller,
whether it’s Vission 20/20 or Vission.
IP Address:
• Displays the IP Address of the Slave Compressor.
Device ID:
• Displays the Device ID of the Slave Compressor.
CFM:
• Displays the CFM of the Slave Compressor.
Figure 10-6. Compressor Sequencing Screen - Device List (Page 4)
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......