13 – 7
Section 13
•
Instruments Calibration
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 13-8. Instruments Calibration Screen - Analog Outputs (Page 6)
Analog Outputs
The Analog output card of the Vission 20/20 generates
a 4–20mA signal to any attached devices. However, it is
not uncommon that a small difference in the board com-
ponents might result in a small difference in the output.
So this screen offers the operator the ability to fine tune
the upper and lower output values, see Figure 13-8.
Test Limits:
• By pressing either the Test Min or Test Max buttons,
the output will go to either 4mA or 20 mA. The op-
erator can then measure the output for accuracy.
Min (mA):
• If the 4mA output has an unacceptable amount of
error, the operator can use the “+” & “-” buttons to
adjust the output.
Max (mA):
• If the 20mA output has an unacceptable amount of
error, the operator can use the “+” & “-” buttons to
adjust the output
Offset (mA):
• By entering the value of the error from the calibrated
value and the actual value into the offset entry box,
that error will be added/subtracted from the mA val-
ue. The offset is applied to the mA value which should
correct the error. Resolution of error should not be
less than 0.01.
Apply Changes:
• Min (mA) and Max (mA) values are stored to data-
base on by pressing this button. The offset (mA) val-
ue which is used to correct 4mA or 20mA output is
hence not saved until this button is pressed.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......