7 – 12
Section 7 • Alarms and Trips
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
High Discharge Superheat Run Temp (Discharge Superheat Temperature)
This message will appear when the Discharge Superheat Temperature exceeds the safety setting of the High
Superheat Start Temp Trip Setpoint. [Running]After a time delay, (setting of the High Superheat Temperature
Safety Changeover timer), the High Superheat Start Offset Temperature is bypassed and High Superheat Run
Temperature alarm and safety setpoints become active.
See Figure 7-5.
High Superheat Run Temp
Alarm
High Superheat Run Temp
Trip
Discharge Superheat
Temperature > Discharge
Superheat Run Alarm
Temperature
Discharge Superheat
Temperature > High
Discharge Superheat Run
Temperature Trip
High Discharge Temp (Discharge Temperature)
See Figure 7-5.
High Discharge Temp
Warning
High Discharge Temp
Inhibit
High Discharge Temp
Alarm
High Discharge Temp Trip
Discharge Temperature
> High Discharge
Temperature Alarm
Discharge Temperature
> High Discharge
Temperature Alarm
Discharge Temperature
> High Discharge
Temperature Alarm
Discharge Temperature
> High Discharge
Temperature Trip
Low Discharge Temp (Discharge Temperature)
This is not a user adjustable setpoint. The value is used to test for a failure in the measuring instrument.
Low Discharge Temp
Warning
Low Discharge Temp
Inhibit
Low Discharge Temp Trip
Discharge Temperature <
-100 °F
Discharge Temperature <
-100 °F
Discharge Temperature
< Low Discharge
Temperature Trip [-100 °F]
Emergency Shutdown Activated
Emergency Shutdown
Activated
Compressor in False
Start Condition After
Emergency Stop Timer
times out
False Start
False Start
Motor Auxiliary Contact
Fails to Open
False Start
False Start
Motor Amperage > 20%
Maximum Amps
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......