7 – 11
Section 7 • Alarms and Trips
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
High Discharge Pressure (Discharge Pressure)
This message will appear when the Discharge Pressure exceeds the safety setting of the High Discharge
Pressure Alarm (or Trip) Setpoint No.1 or No. 2.
See Figure 7-3.
High Discharge Pressure
Warning
High Discharge Pressure
Inhibit
High Discharge Pressure
Alarm
High Discharge Pressure
Trip
Discharge Pressure > High
Discharge Pressure Alarm
Setpoint No. 1 or No. 2
Discharge Pressure > High
Discharge Pressure Alarm
Setpoint No. 1 or No. 2
Discharge Pressure > High
Discharge Pressure Alarm
Setpoint No. 1 or No. 2
Discharge Pressure > High
Discharge Pressure Trip
Setpoint No. 1 or No. 2
Low Discharge Pressure (Discharge Pressure)
This is not a user adjustable setpoint. The value is used to test for a failure in the measuring instrument.
Low Discharge Pressure
Warning
Low Discharge Pressure
Inhibit
Low Discharge Pressure
Trip
Discharge Pressure < -66.5
psig
Discharge Pressure < -66.5
psig
Discharge Pressure < Low
Discharge Pressure Trip
[-66.5 psig]
Discharge Superheat Temperature
These safeties are active when superheat monitor is enabled in the configuration screen. Superheat
Temperature depends on Discharge Pressure and Discharge Temperature.
High Discharge Superheat Start Temp (Discharge Superheat Temperature)
This message will appear when the Discharge Superheat Temperature exceeds the safety setting of the High
Superheat Start Temp Trip Setpoint.
See Figure 7-5.
High Superheat Temp
Warning
High Superheat Temp
Inhibit
High Superheat Start Temp
Trip
Discharge Superheat
Temperature > High
Discharge Superheat Start
Temperature Trip
Discharge Superheat
Temperature > High
Discharge Superheat Start
Temperature
Discharge Superheat
Temperature > High
Discharge Superheat Start
Temperature Trip
High Discharge Superheat Rise Temp (Discharge Superheat Temperature)
This message will appear when the Discharge Superheat Temperature exceeds the safety setting of the High
Superheat Start Temp Trip Setpoint. [Starting]After a time delay, (setting of the High Superheat Temperature
Safety Changeover timer), this safety is deactivated and the High Superheat Run Temperature alarm and safety
Setpoints become active. The trip will be activated if the superheat temperature from start rises above the
superheat temperature plus the Setpoint value.
See Figure 7-5.
High Superheat Rise Temp
Trip
Discharge Superheat
Temperature > Discharge
Superheat Start
Temperature Offset
Warnings
Inhibits
Alarms
Trips
Not Running (Idle)
Pre-Start
Running
Running
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......