10 – 2
Section 10
•
Compressor Sequencing
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
name can be selected from the drop-down list. The
same Equipment name should not be configured
more than once in the sequencing table.
Control:
• Inclusion/exclusion of compressor partaking in the
sequencing can be decided on basis of this toggle
button. Compressors can be included/excluded by
toggling ON/OFF.
NOTE
Switching a compressor control to OFF when
running in Auto Seq mode puts the respective slave
compressor into local auto mode. This feature is
used to add or remove slave compressors from the
sequence table when running in Auto Seq mode.
Priority:
•
This defines the priorities of the compressors on the
network. This priority will decide the sequence in
which compressors will be turned on and off during
the sequence cycle. The lower the priority number,
the greater the priority of the compressor.
Step:
• This parameter would decide the stepwise increase
or decrease value in percentage of the compressor
capacity. In the case the last step makes the total ca-
pacity greater than the maximum capacity, total ca-
pacity will get reduced to maximum capacity. Same
is applicable when the last step makes the total ca-
pacity lower than the minimum capacity, then mini-
mum capacity takes priority.
Min Cap:
•
Defines the lowest capacity in percentage at which
a compressor is allowed to run. Minimum capacity
value has precedence over first step value.
Max Cap:
•
Defines the highest capacity in percentage at which
a compressor is allowed to run. Maximum capacity
value has precedence over last step value.
Status Symbols:
• The status symbols show status of Slave compressors
on the sequencing table, see Table 10-1. For further
details, see Application Notes.
Machine Start Timer:
• Machine Start timer shows the time in seconds that
the Master Compressor will hold before starting slave
compressor once the Start decision is taken.
Machine Stop Timer:
• Machine Stop timer shows the time in seconds that
the Master Compressor will hold before stopping
slave compressor once the Stop decision is taken.
Accelerated Shut Down Timer:
• Accelerated Shut Down timer shows the time in sec
that the Master Compressor will hold before stopping
slave compressors due to Auto-Cycle Stop Setpoint.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......