Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Step 2: Setup and selection of Oil Cooling from
page 2 of the Configuration screen
The oil cooling VPLUS algorithm must be enabled from
the configuration screen. The algorithm used for this
is the same one that is used to control the oil cooling
motorized positioning valve. Navigate to page 2 of the
Configuration screen. In the middle column, towards
the bottom of page 2 are the Oil Cooling selections, see
Figure B-33. Select “Liquid Injection” method and then
select the “Motorized Valve” selection. Note that by
selecting the positioning valve algorithm, the speed of
the VPLUS motor is being controlled based on the dis-
charge temperature only (by default), but the settings to
be established in step 3 will provide additional control
variables.
Continue to step 3.
Figure B-33. Oil Cooling Selection for VPLUS Oil Cooling