6 – 8
Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 6-10. Compressor Control Screen - Rapid Cycling VFD Control
Rapid Cycling VFD Control
Operation at variable speed provides constant load-
matching capacity and energy saving by eliminating
over-capacity running.
However, refrigeration compressors that use speed con-
trol are operated outside the normal area of operation
defined and specified by the manufacturer. It is there
-
fore very important to take into consideration certain
electrical and refrigeration technology restraints.
That is why this is a Special Compressor Setting that only
a Vilter
TM
user can activate, with knowledge of installa-
tion data, to make sure the equipment you have is com-
pa-tible with the set up, and that you have available all
hardware (such as Digital Input/Output Card #5, that will
allow you to control the Oil Restriction Solenoid), so that
the Rapid Cycling VFD Control can work fluidly in your
application.
If at any point changes are made to your application,
configuration or equipment, you will need to consult a
Vilter
TM
engineer on how to apply those changes to the
use of the Rapid Cycling VFD Control feature.
The VFD page is where the operator can tune the motor
VFD for desired rapid cycling VFD operation, see Figure
6-10. A Vilter
TM
compressor uses the variable speed of
a VFD controlled motor to vary the amount of work or
capacity of the compressor. The rapid Cycling VFD con-
trol will keep the capacity slide loaded to maximum and
vary the motor speed to achieve the required work or ca-
pacity. For example, if the compressor needs to load to
100% of its capacity. The control algorithm will keep the
capacity slide loaded to its maximum position and ramp
up the motor speed up to its maximum speed. In the un-
loading direction, the motor speed will ramp down to its
minimum speed, keeping capacity slide loaded to maxi-
mum. In this manner, capacity load is handled by vary-
ing motor speed only. Oil Restriction Solenoid Function
will be automatically enabled when Rapid Cycling VFD
is selected in Configuration Screen. Refer to the Oil
Restriction Solenoid Section for Oil Restriction Setpoint
details.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......