B - 16
Appendix B
•
Vission 20/20 Application Procedures
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
MASTER COMPRESSOR SEQUENCING MENU
SETUP
The master compressor loads and unloads itself based
on the proportional control settings that are set in its
own Compressor Control Setpoints menu. The Auto-
cycle Setpoints can also be enabled for the master com-
pressor, which would define the setpoints for when the
master compressor will stop and start. Auto-cycle set-
tings on the slaves are not active during sequencing;
however you still may wish to select Auto-cycle on the
slave compressor for the circumstance where the power
is removed from the Master panel, and the slave com-
pressors would then revert to “Local” control.
The master compressor controls the slave compressors
based on the master compressor control setpoints as
well as the setpoints entered in the master compressor
sequencing menu. Page 2 of the master compressor
sequencing menu (see Figure B-8) allows the operator
to view and adjust settings which are used for compres-
sor sequencing. The pressure / temperature control set-
points and capacity load / unload timers to accomplish
sequencing control are defined here:
1. Start Offset
2. Suction Pressure / Process Temperature /
Discharge Pressure Control Setpoint
3. Fast Load Offset
4. Fast Unload Offset
Start Offset
•
Defines the offset from pressure/temperature con
-
trol setpoint to start a slave compressor. If suction
pressure / process temperature surpasses the start
offset setpoint and master compressor capacity
has reached the max trigger setpoint then the se-
quencing algorithm allows the starting and loading
of the slave compressors to cater to increasing load
requirements.
Suction Pressure / Process Temperature / Discharge
Pressure Control Setpoint
• The target setpoints are read-only values here.
These setpoints can be changed by logging on
Figure B-8. Slave Compressor(s) Loading and Unloading Setup
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......