6 – 14
Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
Figure 6-14. Compressor Control Screen - Control Mode (Oil Control for No Oil Pump)
Stop Load and Force Unload
The stop load and force unload feature’s primary pur-
pose is to attempt to prevent the compressor from
tripping off due to a particular instrument reading. For
example, if the suction pressure drops too low, the com-
pressor will trip off for safety reasons. However, the stop
load & force unload algorithm recognizes a potential trip
and either stops the compressor from loading up or even
unloads the compressor to prevent the trip.
Stop load:
• When this value is reached, the capacity slide will not
advance in any condition.
Force Unload:
• When this value is reached, the capacity slide posi-
tion will decrease until the variable reading is below
this value.
High Motor Amps:
• The motor current values for stop load and force
unload.
High Discharge Pressure:
• Discharge pressure value for stop load and force
unload.
Low Suction Pressure:
• Suction pressure values for stop load and force unload
High Discharge Superheat:
• Discharge temperature superheat values for stop
load and force unload. This is only used for Cool
Compression.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......