6 – 18
Section 6
•
Compressor Control
Vission 20/20 • Operation and Service Manual • Emerson • 35391SC 2.7
1. Use only if the compressor is tripping off for low
oil temperature due to large overshoots and all other
tuning methods have failed.
Avg. with Oil Manifold Temperature:
• When enabled, averages the Oil manifold tempera-
ture and the discharge temperature. This creates a
more stable control variable and should result in more
stable control.
• This selection should be determined by the operator
through testing.
NOTE
For more information on oil cooling setups, see
Appendix B.
Dual Liquid Injection
The Dual Liquid Injection controls the Liquid Injection #
2 digital output. The Liquid Injection # 2 digital output
is controlled depending on Liquid Pressure and Slide
% value. Refer to Figure 6-16 for Dual Liquid Injection
Setpoints.
Dual Liquid Injection:
• This check-box is used to Enable the Dual Liquid
Injection Feature. The Enable/Disable functionality of
this box depends on Selected Compressor Type and
Model in the Configuration Screen.
Valve Loss:
•
This Setpoint defines the Valve Train Loss for the Dual
Liquid Injection Feature.
Safety Loss:
•
This Setpoint defines the Safety Loss for the Dual
Liquid Injection Feature.
Slide %:
•
This Setpoint defines Slide % Value. The Liquid Injection
# 2 digital output depends on this setpoint.
Liquid Pressure:
• This is the measured value at available Dual Liquid
Injection port.
Switch Pressure:
• This value is used to control the Liquid Injection # 2
digital output. When the Liquid Pressure is less than
the Switch pressure then Liquid Injection # 2 digital
output will be Turned OFF. When the Liquid Pressure is
greater than Switch Pressure & Slide Position is greater
than the Slide % Setpoint Liquid Injection # 2 digital
output will be Turned ON.
Orifice Loss:
•
This is the measured value for liquid port orifice Loss.
Port Selection:
• User can select the “Low-Medium”, “Low-High” or
“Medium-High” port option. This selection depends
on Compressor Type & Compressor Model.
Содержание Vilter Vission 20/20
Страница 1: ...Vission 20 20TM Micro controller Operation and service manual Version 2 7 ...
Страница 2: ......
Страница 4: ......
Страница 220: ...B 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 7 ...
Страница 300: ...D 2 Blank Vission 20 20 Operation and Service Manual Emerson 35391SC 2 6 ...
Страница 336: ......
Страница 337: ......